Tighten the top support hardware.
Re-tighten the floor anchor bolts.
STOP. This procedure is complete.
To mount a rack to floor for seismic installation
Verify the rack is unpacked as described in
the floor is properly prepared as described in Chapter 3.
Position the rack over the anchoring hole pattern.
Position the two slotted adapter plates from the rack kit over the drilled holes.
a
If the supplied adapter plate is 0.5 in. (12.7 mm) thick, install one over each slot in the
adapter plate.
b
If the supplied adapter plate is 0.25 in. (6.35 mm) thick, install two over each slot in the
adapter plate.
Note — One 0.25 in. (6.35 mm) thick adapter plate can be used to help
set the minimum embedment mark on the anchor at or below the concrete
surface.
c
Tap an assembled anchor bolt through the adapter plates into each of the four drilled
anchoring holes; see Figure 18.
Note — The anchor bolt should be seated firmly against the adapter
plates and the equipment rack. If the bolt protrudes or if the assembly is
loose, re-drill to a greater depth and use the longer anchor bolts.
3HH-12893-AAAA-TCZZA
"Unpacking and inspection"
DRAFT
Installing racks
and make sure that
71