7360 ISAM FX-16 shelf cabling
5
6
7
8
9
10
11
Procedure 18
Use the following procedure when the power cables need to be disconnected on 7360 ISAM FX-
16.
1
2
3
4
5
110
Tighten the nuts back on the power terminals with a torque of 65 lbf-in. maximum.
Place the safety cover back in its location and fasten the screws.
Turn on the A and B power from the power distribution frame to the rack.
Verify that the BAT A and BAT B LEDs are green.
Switch the A and B circuit breakers to the ON position.
Verify that the fans spin.
STOP. This procedure is complete.
To disconnect the power cables
Warning — If the following sequence is not followed exactly, there can
be a possible fire hazard.
Before disconnecting the power cables, ensure that power to the cables has been
disconnected.
Switch off the circuit breakers for BAT A and BAT B
Disconnect the battery cables BAT A and BAT B
Disconnect the BATRET cables RET A and RET B
STOP. This procedure is complete.
3HH-12893-AAAA-TCZZA
ANSI Hardware Installation Manual
DRAFT