ANSI Hardware Installation Manual
Procedure 8
1
2
Issue: 09
shop vacuum
socket set, 3/8-in. drive with ratchet handle and extensions
torque wrench
Do not use a shelf as a handhold (or foothold)
Danger 1 —
when lifting the rack.
Brace the top of the rack during movement to
Danger 2 —
prevent tipping, and avoid strains that might twist or otherwise
damage the shelf backplane.
For installation at sites prone to seismic shock, the rack
Note —
installation is effective only on concrete flooring with a minimum
thickness of 6.25 in. (15.88 cm), a minimum strength of 3000
psi (20 684 kPa), and with 0.5% steel rebar reinforcement. In
cases where the longer concrete anchor (M12/50) is being
used, the concrete should be a minimum of 7.25 in. (18.42 cm)
thick.
To mount a rack to floor for non-seismic installation
Verify the rack is unpacked as described in
the floor is properly prepared as described in Chapter 3.
Install a floor anchor in each hole and set with the setting tool; see Figure 15. The anchor is
fully seated when the tool is flush with the top of the anchor.
3HH-12893-AAAA-TCZZA
"Unpacking and inspection"
DRAFT
Installing racks
and make sure that
67