Mounting Of Power Cable Shoes And Safety Cover On 7360 Isam Fx- 12 - Nokia 7360 Intelligent Services Access Manager FX Series Hardware Installation Manual

Ansi
Hide thumbs Also See for 7360 Intelligent Services Access Manager FX Series:
Table of Contents

Advertisement

7360 ISAM FX-12 shelf cabling
Figure 82
3
4
5
6
7
8
9
178
Mounting of power cable shoes and safety cover on 7360 ISAM
FX-12
Remove the nuts from the power terminals; see Figure 82.
Danger — If the following sequence is not followed exactly, there can
be a possible fire hazard.
Guide the power cables through the cable guide and connect them to the power terminals as
follows; see Figure
81
showing the cables connected:
Note — The RET A and RET B connections are on a common ground.
first connect the BATRET cables RET A and RET B
then connect the battery cables BAT A and BAT B
Tighten the nuts back on the power terminals with a torque of 13.28 to 17.7 lbf-in. (1.5 to 2.0
N.m).
Place the safety cover back in its location and fasten the screws.
Turn on the A and B power from the power distribution frame to the rack.
Verify that the BAT A and BAT B LEDs are green.
Switch the A and B circuit breakers to the ON position.
3HH-12893-AAAA-TCZZA
ANSI Hardware Installation Manual
DRAFT
22383
Issue: 09

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7360 isam fx-16

Table of Contents