ANSI Hardware Installation Manual
9 Installing a 7360 ISAM FX-12 shelf
9.1 Overview
This chapter provides the steps to install a 7360 ISAM FX-12 shelf in a standard CO
equipment rack, including procedures for:
•
•
The 7360 ISAM FX-12 is suitable for the following:
•
•
•
Issue: 09
9.1 Overview
9.2 Mounting the 7360 ISAM FX-12 shelf
9.3 Installing a 7360 ISAM FX-12 heat and fiber baffle kit
9.4 Replacing the fan unit in a 7360 ISAM FX-12 shelf
Mounting the 7360 ISAM FX-12 shelf
Replacing the fan unit in a 7360 ISAM FX-12 shelf
The 7360 ISAM FX-12 is intended to be installed in
Warning —
a restricted access location (RAL) in accordance with the
applicable requirements of NEC or CEC. The local authorities
have jurisdiction. This unit is intended to be installed by
qualified service personnel only. Observe the following for the
7360 ISAM FX-12.
•
Connect to a reliably grounded −48 V dc SELV source that
is grounded in the same building.
•
Provide branch circuit overcurrent protection that is rated as
80 A with 2 AWG copper conductors.
•
Incorporate a readily accessible disconnect device that is
suitably approved and rated in the field wiring.
rack mounting on concrete floors or other non-combustible surfaces with the use
of a heat and fiber baffle kit
use in an installation using an IBN or a CBN
use in:
•
network telecommunication facilities
•
locations where the NEC applies
•
OSP
3HH-12893-AAAA-TCZZA
Installing a 7360 ISAM FX-12 shelf
DRAFT
153