Enabling Of The Function; Position Values For Damper Actuators - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

K NX
CO
R
K N X
CO
R
Note
Siemens
Building Technologies
8.6.2

Enabling of the function

The function can be centrally disabled or enabled.
Basic setting: the outside air damper is enabled.
The following S-mode communication object is used to integrate the damper enabling:
Enable dampers (Input communication object)
Flags
Type
R W K T U
0 1 1 0 0 1.003
DPT_Enable
The following communication object is used in LTE-mode:
Enable dampers (Input)
Possible partner function blocks
115 HVACOpt
DisableDamper
HVAC-Optimizer
Geographical
zone
The use of the outside-air damper can only be implemented in conjunction with the
RXB21.1 controller. In this case, the AC 24 V 3-position damper actuator is connected
to the outputs Y3 and Y4.
8.6.3

Position values for damper actuators

The position of the outside air damper is mapped to the bus.
In S-mode, the following communication object is used for this purpose:
Outside air damper (Output communication object)
Flags
Type
R W K T U
1 0 1 1 0 5.001
DPT_scaling
In LTE mode, the "position" of the outside air damper is transmitted as follows:
Outside air damper (Output )
ActPosSetpFreshAir
Geographical zone
If the LTE bus information is not required, it can be disabled (see pages 90 and 143 for
notes on reducing the load on the bus).
RXB (KNX) application library
Control sequences
Receive timeout
yes
Send heartbeat
yes
Possible partner function blocks
362 ADA
Air Damper Actuator
FNC Description of functions for FC-10, FC-11, FC-12
States
0 = Disable = damper closed
1 = Enable = automatic control
Known partner devices
Siemens:
---
Value
0...100%
0 = 0%
255 = 100%
Known partner
devices
---
CM110385en_05
28 Feb 2009
107/166