Bus Supply For Rxb Controllers; Rxb Konnex Controller Communications; S-Mode - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Siemens
Building Technologies
1.7

Bus supply for RXB controllers

RXB controllers can work without bus supply if the following conditions are adhered to:
• Parameterize only using the HandyTool (not with ETS3 or ACS).
• No integration in a building automation and control system (e.g. DESIGO, Synco).
• No changeover mode (sensor signal via bus).
• No outdoor temperature via bus
• No master/slave combinations.
Otherwise, the Konnex bus, used by the RXB room controller for communication,
requires a bus supply.
Each controller consumes 5 mA. The supply has to be selected according to the
number of controllers. We recommend the following products:
Manufacturer
Siemens Building Technologies
Siemens Automation and Drives
1.8

RXB Konnex controller communications

RXB Konnex controllers support communication as per the Konnex specification.
Among the modes defined in this specification are the following:

• S-mode

= Standard mode
• LTE mode = Logical Tag Extended Mode
This is a new mode which supports simpler
engineering and is used in conjunction with Synco.
1.8.1
S-mode
This mode corresponds to EIB communication. Connections are established via ETS3
Professional and group addresses.
This ensures a link to the existing EIB environment.
For more details of this mode, refer to the EIB manual.
RXB (KNX) application library
Introduction
Type
ACX95.320/ALG
5WG1 125-1AB01
5WG1 125-1AB11
5WG1 125-1AB21
FNC Description of functions for FC-10, FC-11, FC-12
Designation
Power supply 320 mA
Power supply 160 mA
Power supply 320 mA
Power supply 640 mA
9/166