Siemens Desigo RXB Technical Manual page 408

Technical manual
Table of Contents

Advertisement

Configuration
Menu
Communication
Room temperature setpoints
Sequences
LTE mode Heating outp bus valve
Motorized and electromechanic Runtime
Motorized Offset
Fan control.
Room unit
With LCD Display heating/cooling symbols
General functions.
Central functions
Master/slave
6/52
Siemens
Building Technologies
The following parameters are available with application FNC02.
They are set via ETS, ACS, or HandyTool.
Parameters.
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Control sequence
Actuator type heat/cool valve
Cooling outp bus valve
Fan speeds
Fan control.
Minimum on time.
Temperature sensor B1
Periodic fan kick Comfort
Periodic fan kick Economy
Measured value correction
Setpoint offset range
Local Comfort mode
Room unit
Temperature unit
Standard display
Setpoint display
Digital input 1
Free (bus = 1)
Occupancy: Occupied
Window:
Digital input 2
Free (bus = 1)
Occupancy: Occupied
Window:
Temporary Comfort mode
On-delay occupancy detector
Off-delay presence detector
Heating demand signal
Cooling demand signal
Boost heating
Precooling, free cooling
Reset setpoint offset
Master/slave
RXB application library (KNX)
FNC02 – Two-pipe fan coil with changeover
Values/Range
S-mode / LTE and S-mode
0 ... 105 min.
0 ... 105 min.
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
– Heating only
– Cooling only
– Changeover
– STA71
– STA72E
– STE71
– STE72
– STP71
– STP72E
– Electromech. 3rd devices
– Motorized 3
rd
– Thermal 3
– Motorized bus
Off/On
Off/On
0 ... 360 s
0 ... 360 s
– External control
– 1-speed/2-speed/3-speed
Manual / Auto
1 ... 10 min
– Room
– Return air
– Measured value only
– No sensor
0 ... 90 min (90min = Off)
0 ... 360 min (360min = Off)
– 3 ... 3 K
± 0 ... 10 K
Enabled / Disabled
Without LCD / with LCD
Enabled / Disabled
°C or °F
No display / Room
temperature / Setpoint
Absolute / Relative
= Contact open/closed
= Contact open/closed
Window open
= Contact open/closed
= Contact open/closed
= Contact open/closed
Window open
= Contact open/closed
0 ... 360 min
0 ... 90 min
0 ... 90 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
Basic setting
S-mode.
60 min.
45 min.
40 °C
35 °C
28 °C
24 °C
21 °C
19 °C
15 °C
12 °C
Cooling only
– SSA81
STP72E
– SSB81
– SSP81
– SQS81
rd
devices
devices
Off
Off
150 s
0 s
3-speed
Auto
6 min
No sensor
90 min (Off)
360 min (Off)
0 K
± 3 K
Enabled
Without LCD
Enabled
°C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
60 min
5 min
5 min
Enabled
Enabled
Enabled
Enabled
Disabled
Master
CM110672en_03
30.11.2007

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents