Values Representing Chilled Ceiling Valve Actuator Positions - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Motorized and electromechanic valves
HandyTool
Parameter
Running time cool surf valve
Offset cooling surface valve
Important!
STOP
K N X
CO
R
Note
88/140
Siemens
Building Technologies
Basic setting
150 s
0 s
8.2.2
Values representing chilled ceiling valve actuator
positions
The position of the chilled ceiling valve is mapped to the bus.
The Cooling surface output communication object must NOT be used for applications
for thermal valve actuators to control KNX/EIB valve actuators. With these applications,
the communications objects have theoretical valve positions only.
Valve positions are available in the following S-mode communication objects:
Cooling surface output (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 5.001
DPT_Scaling
If KNX / EIB bus actuators (S-mode) are integrated in DESIGO, the flags must be
checked: delete read access at actuator!
As there are different manufacturers for EIB/KNX bus actuators, the name of the S-
mode communication object varies.
The valve position in LTE mode is transferred as follows:
Cooling surface output (output)
ActPosSetpCoolStageA
Geographical zone
RXB (KNX) Applications library
Control sequences
Range
0 ... 360 s
0 ... 360 s
Send heartbeat
Yes
Possible partner function blocks
352 HVA
HVAC Valve Actuator
CLC and RAD description of functions for CC-02 CM110384en_03
Resolution
HandyTool
1 s
*052
1 s
*054
Value
0...100%
0 = 0%
255 = 100%
Known partner
devices
---
28 Feb 2009