RMH760
Controller 1
T
T
T
Heat source
DHW heating
Heat requistion
Heat demand
Heat distr zone 1
Setting values
Controller 1
Explanation relating to
the illustration
Notes
30/166
Siemens
Building Technologies
3.4

Heating and cooling demand zone

The building described above is equipped with Synco control equipment on the
generation side.
RMH760
Controller 3
Controller 2
2
T
1
Heating circuit
fan coil
Heat demand
Heat requistion
Heat distr zone
source side: 1
Heat distr zone 2
Controller 2
Controller 3
In the case of a typical application, the individual RXB room controllers - when used
with the RMB central control unit - signal their heat demand directly to the primary
controller (in the above example to the RMH760).
(1) and (2) designate the numbers of the distribution zone.
• This type of application can analogously be applied to refrigeration distribution
zones.
• If no 2-pipe fan coil is used, heat and refrigeration demand signals are sent
simultaneously to the primary plant.
RXB (KNX) application library
Select communication mode
RMB795
RXB...
Controller 4
Fan coil
room A
Heat demand
Heat distr zone 2
Controller 4
FNC Description of functions for FC-10, FC-11, FC-12
Konnex TP1
RXB...
RXB...
Controller 5
Controller 6
Fan coil
Fan coil
room B
room C
Heat demand
Heat demand
Heat distr zone 2
Heat distr zone 2
Controller 5
Controller 6
CM110385en_05
28 Feb 2009