5.5
Determine the room operating mode with
Synco (LTE mode)
In LTE-mode the e ffective room operating mode of the room controller depends on the
central Room operating mode time schedule and/or on local influences such as window
contacts, presence detectors or room units.
The diagram below shows how these influences are processed by the room controller,
and their priority:
Central (ACS)
Central
(Synco controller)
Enable Comfort
LTE
Room operating
mode
LTE
• If the room operating mode in the ACS (operating booklet) is AUTO, the priorities
1 to 3 apply.
If the room operating mode in the ACS (operating booklet) is Comfort , Precomfort ,
Economy or Protection , these modes have absolute priority ("Prio 0").
• The effects of Priority 1 and Priority 2 are similar in nature to states , which apply
continuously
• The Priority 3 influences are treated as events .
The key factor is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies.
RXB (KNX) application library
Room operating modes
Local
Controller
Prio
Window contact
DI
2.
3.
Presence detector
3.
DI
Room unit
PPS2
3.
FNC Description of functions for FC-10, FC-11, FC-12
0.
1.
1.
CM110385en_05
57/166
28 Feb 2009