Morning Boost (Morning Warmup, 2); Precooling (Precool, 5) - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Disable special
functions
ETS3 Professional
HandyTool
Enable function
Start function
Terminate function
106/140
Siemens
Building Technologies
Triggering the special functions by the building automation and control system can be
disabled in each room controller via tool.
Go to the Functions menu for the disable feature.
See parameters in the last column of the above table.
10.8

Morning boost (Morning Warmup, 2)

This function is used to raise the temperature in a room as quickly as possible to the
Precomfort heating setpoint at the end of the night setback period.
Objective: Preheat the room in the event of heating.
Y [%]
100
0
SpH
The following conditions must be fulfilled:
• The room controller must be in Economy room operating mode.
The function can be disabled in the room controller with ETS3.
The function must be enabled via the building automation and control system
(communication object Application mode , see page 105).
The function is disabled via the building automation and control system.
10.9

Precooling (Precool, 5)

This function is used to cool rooms to the Comfort cooling setpoint prior to actual
occupancy.
Y [%]
100
0
SpH
SpC
Cmf
RXB (KNX) Applications library
General / central functions
TR
SpC
Stby
Stby
TR
Cmf
CLC and RAD description of functions for CC-02 CM110384en_03