10.1.1 Window switch (S-Mode)

For master/slave mode, only the master's window switch is evaluated without special
measures, which also influences the slave controllers.
If another window switch is also connected to the slave, it is NOT considered unless
you create the following binding:
Window contact Input
DI
This binding ensures that both controllers react when a window is opened.
If several slaves are equipped with window switches, the correct evaluation is required
for the logic block.

10.1.2 Presence detector (S-mode)

For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
If another presence detector is also connected to the slave, it is NOT considered unless
you create the following binding:
Presence detector Input
DI
This binding ensures that both controllers react when a presence detector becomes
active.
If several slaves are equipped with presence detectors, the correct evaluation is required
for the logic block.
RXB (KNX) application library
Master/slave
Master
Master
FNC Description of functions for FC-10, FC-11, FC-12
Slave
Window contact Output
DI
Slave
Presence detector Output
DI