Siemens Desigo RXB Technical Manual page 431

Technical manual
Table of Contents

Advertisement

Connection diagram
List of equipment
Note
Siemens
Building Technologies
B1
D1
2)
D2
2)
YH
T
1
2
3
4
5
6
19
19
21 21
AC 230 V
N
L
Ref.
Description
N1
Room controller.
R1
Room unit
B1
Supply air temperature sensor.
D1
Window contact
D2
Presence detector
Q1
1- or 3-speed fan
YH
Heating valve actuator, motorized,
3-position control
YC
Cooling valve actuator, motorized,
3-position control
2) Type of operation (N/O or N/C) can be selected.
3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873).
4) Do not connect the fans in parallel (or use cut-off relays).
A current list of compatible devices is available in the DESIGO RX hardware overview
(N3804).
RXB application library (KNX)
FNC08 – Four-pipe fan coil with room supply air cascade
YC
R1
3)
3)
QAX...
M
M
7
8
9
10 11 12 13 14 15 16
25 26 27
28
Q1
4)
2)
.
2)
.
4)
.
3)
.
3)
.
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
KNX
N1
17 18
RXB21.1
29/52
CM110672en_03
30.11.2007

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa