Desigo Examples - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Example 1
44/166
Siemens
Building Technologies
The resultant Effective room operating mode is also available as 4 digital
communication objects:
Effective room operating mode Comfort (output communication object)
Effective room operating mode Precomfort (output communication object)
Effective room operating mode Economy (output communication object)
Effective room operating mode Protection (output communication object)
Flags
Typ
L S K Ü A
1 0 1 1 0 1.001
DPT_Switch
5.3.8

DESIGO examples

The following are examples of two typical applications of time schedules in conjunction
with local control of the room operating mode.
Rooms with neither a room unit nor a presence detector
The operating mode of Rooms 1 ... 3 in a building is determined by the two time
schedules Building use and Room occupancy . Window contacts are fitted in all rooms.
The following conditions are specified:
• Overall, the building is in use from 06.00 to 22.00 ( Building use time schedule).
Outside this period the opening of a window will trip an alarm (2).
• Rooms 1...3 are used by the same tenant and controlled by the same O ccupancy
time schedule. Night mode is to operate from 17.00 to 08.00 (Unoccupied) and the
lunch break is from 12.00 to 13.00 (Standby).
• In Room 3 the window is opened briefly, once in the morning and once at night (1).
RXB (KNX) application library
Room operating modes
Send Heartbeat
Ja
FNC Description of functions for FC-10, FC-11, FC-12
Zustände
0 = Aus
1 = Ein
CM110385en_05
28 Feb 2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents