In LTE mode, the room/return air temperature from directly connected sensors is
mapped as follows:
Room temperature output (Output)
TempRoom
Geographical zone
Return air temperature output (Output)
TempReturnAir
Geographical zone
7.1.6

Temperature sensor input from Konnex bus

The signal from the sensor connected to the bus takes priority. The signal is not
averaged and no sensor correction (page 140) is done.
Since KNX temperature sensors are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
KNX temperatur sensor
... or ...
If the room temperature/return temperature is available as information on the bus, it can
be read with one of the following S-mode communication objects:
Room temperature input (Input communication object)
Return air temperature input (Input communication object)
Flags
Type
R W C T U
0 1 1 1 1 9.001
DPT_Value_Temp
Subject to the appropriate configuration and integration, the room temperature/return
air temperature is read by the controller immediately after a reset.
For a Konnex sensor the send heartbeat must be set to "Cyclical sending enabled"
RXB (KNX) application library
Temperature measurement
Possible partner function
blocks
390 UHD
UserHVACDisplay
Possible partner function
blocks
---
RXB... room controller
RaumTemperatur
Room temperaure Input
Return air temperature Input
Receive timeout
yes
FNC Description of functions for FC-10, FC-11, FC-12
Known partner devices
Siemens:
Synco RMH760 / RMB795
RMU710 / 20 / 30
Known partner devices
---
10385Z16en
EffektiveRaumTemperatur
Effective Room temperature
Effective Room Temperature
Value
Floating point (°C)
79/166
CM110385en_05
28 Feb 2009