Temperature sensor input from Konnex bus

The signal from the sensor connected to the bus takes priority. The signal is not
averaged and no sensor correction (page 115) is done.
Since KNX temperature sensors are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
KNX Temperature sensor
If the room temperature is available as information on the bus, it can be read with one
of the following S-mode communication objects:
Room temperature input (input communication object)
Flags
Type
R W C T U
0 1 1 1 1 9.001
DPT_Value_Temp
Subject to the appropriate configuration and integration, the room temperature is read
by the controller immediately after a reset.
For a Konnex sensor the send heartbeat must be set to "Cyclical sending enabled"
Room temperature (input)
Possible partner function blocks)
TempRoom
321 RTS
Room Temperature Sensor
Geographical zone
RXB (KNX) Applications library
Temperature measurement
RXB... Room controller
Room temperature input
RaumTemperatur
Receive timeout
Yes
CLC and RAD description of functions for CC-02 CM110384en_03
10384Z16en
Effective room temperature
EffektiveRaumTemperatur
Value
Floating point (°C)
Known partner devices
Siemens:
Synco RMH760
RMU710 / 20 / 30
QAW740
77/140
28 Feb 2009