Local Control Of Room Operating Mode Via A Window Contact - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Effective room operating
mode
Window contact
K N X
CO
R
34/140
Siemens
Building Technologies
5.3.1
Local control of room operating mode via
a window contact
Central
Local
Controller
Prio
S
1.
DI
2.
S
3.
S
S
DI
3.
PPS2
3.
S
The table below shows the Effective room operating mode as a function of the window
contact input.
Window contact
status
Window closed
Window open
The window contact is connected directly to a digital input on the room controller (see
page 102). Alternatively an EIB/KNX window contact (connected to the bus) may be
used. The application evaluates both items of information (logic OR operation).
Since EIB/KNX window contacts are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
Window contact on DI
EIB / KNX window contact
The following S-mode communication object is used to integrate an EIB/KNX window
contact:
Window contact input (Input communication object)
Flags
Type
R W C T U
0 1 1 0 0 1.019
DPT_WindowDoor
RXB (KNX) Applications library
Room operating modes
If a window is opened, the room controller always
switches to room operating mode Protection , i.e. the
S
heating or cooling output is reduced to a minimum. If a
window is opened outside the building-in-use period, it
is possible to, e.g., trigger an additional alarm in the
S
building automation and control system.
Effective room operating mode
No effect.
Lower-priority inputs determine the operating mode.
Protection.
Raum-Controller RXB...
Window contact input
Receive timeout
No
CLC and RAD description of functions for CC-02 CM110384en_03
OR
Window contact output
10385Z10en
States
0 = Closed
1 = Open
28 Feb 2009