Values Representing Radiator Valve Actuator Positions - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Important!
STOP
K N X
CO
R
Note
Reduce bus load
ETS3 Professional
Note
Siemens
Building Technologies
8.1.2

Values representing radiator valve actuator positions

The position of the radiator valve is mapped to the bus.
The Heating surface output communication object must NOT be used for applications
for thermal valve actuators to control KNX/EIB valve actuators. With these applications,
the communications objects have theoretical valve positions only.
In S-mode, the following communication object is used for this purpose:
Heating surface output (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 5.001
DPT_scaling
Since EIB/KNX bus actuators are available from a variety of manufacturers, the name
of the S-mode output communication object varies accordingly.
If KNX / EIB bus actuators (S-mode) are integrated in DESIGO, the flags must be
checked: delete read access at actuator!
In LTE mode, the radiator position is transmitted as follows:
Heating surface output (output)
ActPosSetpHeatStageB
Geographical zone
In LTE-mode, where directly connected actuators are used rather than bus valve
actuators, the bus load can be reduced by disabling LTE communication for these
outputs (see also page 118).
Select Sequences .
The two fields at the bottom appear only if "LTE and S-mode" is selected in the
Communication menu.
RXB (KNX) Applications library
Control sequences
Send heartbeat
Yes
Possible partner function blocks)
352 HVA
HVAC Valve Actuator
CLC and RAD description of functions for CC-02 CM110384en_03
Value
0...100%
0 = 0%
255 = 100%
Known partner
devices
---
83/140