Determine The Room Operating Mode With Synco (Lte Mode) - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Note!
STOP
Siemens
Building Technologies
5.5
Determine the room operating mode with
Synco (LTE mode)
In LTE-mode, the Effective room operating mode of the room controller depends on the
central room operating mode schedule and/or on local influences such as window
contact, presence detector, or room unit.
The illustration below shows how these influences are processed by the room controller
along with their priority:
Central (ACS)
Central
(Synco controller)
Enable Comfort
LTE
Room operating
mode
LTE
• If the room operating mode in the ACS (operating booklet) is AUTO, the priorities
1 to 3 apply.
If the room operating mode in the ACS (operating booklet) is Comfort , Precomfort ,
Economy or Protection , these modes have absolute priority ("Prio 0").
• The effects of Priority 1 and Priority 2 are similar in nature to states , which apply
continuously
• The influence of priority 3 is treated as event .
The key point in time is the moment at which the state changes (edge).
If another source of third priority later changes the state, the last known change is
valid .
RXB (KNX) Applications library
Room operating modes
Local
Controller
Prio
Window contact
DI
2.
3.
Presence detector
3.
DI
Room unit
PPS2
3.
CLC and RAD description of functions for CC-02 CM110384en_03
0.
1.
1.
55/140