Bus Output For Current Setpoints; Bus Output Effective Setoints; Bus Outputs Lte Mode - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

K N X
CO
R
Note
68/140
Siemens
Building Technologies
6.1.1

Bus output for current setpoints

The present setpoints can be integrated in a building automation and control system
individually or as triplets via the following S-mode communication objects:
Present Eco cooling setp (output communication object)
Present Precomf cool setp (output communication object)
Present Comf cooling setp (output communication object)
Present Comf heating setp (output communication object)
Present Precomf heat setp (output communication object)
Present Eco heat setp
Flags
Type
R W C T U
1 0 1 1 0 9.001
DPT_Value_Temp
Present setpoints heating (output communication object)
Present setpoints cooling (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 222.100
DPT_TempRoomSetpSetF16[3]
6.1.2

Bus output effective setoints

Upon integration in a building automation and control system, the effective setpoints
are mapped by the controller to the following communication objects based on the
Effective room operating mode :
Effective setpoint (output communication object)
Effective setpoint heating (output communication object)
Effective setpoint cooling (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 9.001
DPT_Value_Temp
If the room temperature is in the deadband, the Effective setpoint is transmitted either
as heating or cooling setpoint, depending on whether the controller last was cooling or
heating.
6.1.3

Bus outputs LTE mode

In LTE mode, the current and effective setpoints are not transmitted to the building
automation and control system.
RXB (KNX) Applications library
Setpoint calculation
(output communication object)
Send
heartbeat
Yes
Send
heartbeat
Yes
Send heartbeat
Yes
CLC and RAD description of functions for CC-02 CM110384en_03
Values
Floating Point (°C)
Values
3 floating point values
- Comfort (°C)
- Precomfort (°C)
- Economy (°C)
Values
Floating point (°C)