10.13.2 Lte Mode; Reset Setpoint Shift - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

K N X
CO
R
Display on Synco
device:
Important!
STOP
HandyTool
110/140
Siemens
Building Technologies

10.13.2 LTE mode

Enable alarm info can also be operated in LTE mode. Here, two types of information
are provided: AlarmInfo_CS and AlarmText_CS .
With Synco, the user does not need to deal with this, as connection is opened
automatically.
The device in this case is active on the bus and sends its alarm as soon as it receives
highest alarm priority. This ensures that the control station does not miss alarms.
AlarmInfo_CS (Output)
Possible partner function blocks
AlarmInfo_CS
Broadcast
AlarmText_CS (Output)
Possible partner function blocks
AlarmText_CS
Broadcast
Enable alarm info (input)
Possible partner function blocks
EnableAlarmInfo
Broadcast
Error code
English
RXB room temp. sensor error
4910
4930
RXB room air condensation
4960
RXB general fault
RXB PPS fault
4970
For more information on the alarm concept, refer to "Communication via bus, Synco700
& RXB", CE1P3127.
10.14

Reset setpoint shift

When the system changes from Comfort or Precomfort to Economy or Protection , the
setpoint shift can be reset (see page 72). This function can be enabled and disabled via
Central functions.
The setpoint shift can only be reset with the QAX34.1 and QAX84.1 room units, which
have an LCD display. Enabling this function in room units with a mechanical setpoint
shift (potentiometer) causes data transmission errors.
Parameter
Short name
*137
Reset setpoint shift
RXB (KNX) Applications library
General / central functions
Range
0 = Disabled
1 = Enabled
CLC and RAD description of functions for CC-02 CM110384en_03
Known partner devices
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Known partner devices
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Known partner devices
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Basic setting
Disabled