Determine The Room Operating Mode In Desigo (S-Mode) - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Note!
STOP
Siemens
Building Technologies
5.3
Determine the room operating mode
in DESIGO (S-mode)
In S-mode, the effective room operating mode of the room controller depends on the
central Use and Occupancy time schedules and/or on local influences such as window
contacts, presence detectors or a room unit.
The diagram below shows the priority of these influences and how they are processed
by the room controller:
Central
Local
Window contact
Building use
S
Occupancy
S
Presence detector
Room unit
Temporary Comfort mode
• The effects of Priority 1 and Priority 2 are similar in nature to continuous states
• The Priority 3 influences are treated as events .
The key factor is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies .
RXB (KNX) application library
Room operating modes
Controller
S
DI
S
DI
PPS2
S
FNC Description of functions for FC-10, FC-11, FC-12
Prio
1.
S
Effective
room op.
mode
2.
3.
S
Effective
occupancy
3.
3.
35/166
CM110385en_05
28 Feb 2009