Selection of the control
mode
Electric reheater with
cooling-only or
changeover applications
Heating only
or c/o = Heating
Cooling only
or c/o = Cooling
Changeover with
disabled electric
heater
(see page 97)
96/166
Siemens
Building Technologies
8.4.2
2-pipe fan-coils with electric reheater
YR
YHC
The control mode must be selected at the engineering stage:
heating only, cooling only or changeover
The electric reheater also operates with "Cooling only" and "Change-over" in cooling
mode. In this case, the heating setpoint (SpH) is used for control.
1-step
YR
Y
1 K
H
100%
ON
0%
OFF
YR
Y
H
100%
ON
0%
OFF
Y [%]
Change-over
H
100
YHC
YHC
0
SpH
SpC
Further details: see sections 8.1.3 through 8.1.7.
RXB (KNX) application library
Control sequences
D3
Q1
T
B1
YHC
TR [°C]
SpH
1 K
C
YHC
TR [°C]
SpH
SpC
C
TR [°C]
FNC Description of functions for FC-10, FC-11, FC-12
Y
Output signal
TR
Room temperature
SpC
Effective cooling setpoint
SpH
Effective heating setpoint
H
Heating sequence
C
Cooling sequence
YHC
Heating valve
YR
Electric reheater
Modulating
YR, Y
H
100%
YR
YHC
0%
SpH
YR, Y
H
100%
YR
0%
SpH
CM110385en_05
TR [°C]
C
YHC
TR [°C]
SpC
28 Feb 2009