12.10 Data Point Type Description - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Data point types
ID
Name
1.001
DPT_Switch
1.003
DPT_Enable
1.005
DPT_Alarm
1.017
DPT_Trigger
1.018
DPT_Occupancy
1.019
DPT_Window_Door
1.100
DPT_HeatCool
5.001
DPT_Scaling
5.004
DPT_RelPosValve
6.001
DPT_Percent_V8
8.010
DPT_Percent_V16
9.001
DPT_Value_Temp
9.002
DPT_Value_Tempd
20.002
DPT_BuildingMode
20.003
DPT_OccMode
20.102
DPT_HVACMode
20.105
DPT_HVACContr
Mode
Siemens
Building Technologies

12.10 Data point type description

Instead of the previously referenced EIS data types, this document now references the
new Konnex data point types.
Where possible, the table which follows includes a reference to the corresponding EIS
type.
Format
Unit
B
Bit
(1)
B
Bit
(1)
B
Bit
(1)
B
Bit
(1)
B
Bit
(1)
B
Bit
(1)
B
Bit
(1)
U
%
(8)
U
%
(8)
V
%
(8)
V
%
(16)
F
°C
(16)
F
K
(16)
N
Enum.
(8)
N
Enum.
(8)
N
Enum.
(8)
N
Enum.
(8)
RXB (KNX) Applications library
KNX information
Range / coding
0 = OFF
1 = ON
0 = Disabled
1 = Enabled
0 = No alarm
1 = Alarm
0 = (not used)
1 = Trigger
0 = Unoccupied
1 = Occupied
0 = Closed
1 = Open
0 = Cooling
1 = Heating
0...100%
0 =
255 = 100%
0...100%
0 =
255 = 255%
-100%...+100%
-100 = -100%
+100 = +100%
-100%...+100%
-10000 = -100%
0 =
+10000 = +100%
Floating point
Floating point
0 = Used
1 = Not in use
2 = Protection
0 = Occupied
1 = Standby
2 = Unoccupied
0 = Auto
1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
0 = Auto
1 = Heat
2 = Morning Warmup
3 = Cool
4 = Night Purge
5 = Precool
6 = Off
7 = Test
8 = Emergency Heat
9 = Fan only
10 = Free Cool
11 = Ice
20 = NoDem
255 = NUL
Other: reserved
CLC and RAD description of functions for CC-02 CM110384en_03
Corr. to EIS
EIS1
EIS1
EIS1
EIS1
EIS1
EIS1
EIS1
0%
EIS6
0%
EIS6
(EIS14)
EIS10
0%
EIS5
EIS5
(EIS14)
(EIS14)
(EIS14)
(EIS14)
127/140
28 Feb 2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents