Determine The Room Operating Mode With Third-Party Products (S-Mode) - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Important!
STOP
Siemens
Building Technologies
5.4
Determine the room operating mode
with third-party products (S-mode)
In S-mode, the Effective room operating mode of the room controller depends on the
central Room operating mode schedule and/or on local influences such as window
contact, presence detector, or room unit.
The illustration below shows how these influences are processed by the room controller
along with their priority:
Central
Local
Window contact
Room operating mode
S
Presence detector
Room unit
Temporary
Comfort mode
• The influence of priorities 1 and 2 is equivalent to permanent states .
• The influence of priority 3 is treated as event .
The key point in time is the moment at which the state changes (edge).
If another source of third priority later changes the state, the last known change is
valid .
RXB (KNX) Applications library
Room operating modes
Controller
Prio
S
1.
DI
1.
3.
S
3.
DI
3.
PPS2
3.
S
CLC and RAD description of functions for CC-02 CM110384en_03
S
Effective
room op. mode
S
Effective
occupancy
45/140
28 Feb 2009