Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

DESIGO™
RXB (KNX)
Technical manual
Version 2.37 and higher
CM110389en_06
30 Jun 2009
1
Contents
Selection guide
2
RXC, RXB, RXL, RXA
System overview
3
DESIGO RXB
Hardware overview
4
DESIGO RX
Data sheets RXB (KNX)
Room controllers,
5
Room unit
CLC & RAD
Chilled ceiling and
6
radiator applications
FNC
7
Fancoil applications
RXB, RXL
8
Installation guide
9
10

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Desigo RXB

  • Page 1 DESIGO™ Contents RXB (KNX) Technical manual Selection guide Version 2.37 and higher RXC, RXB, RXL, RXA System overview DESIGO RXB Hardware overview DESIGO RX Data sheets RXB (KNX) Room controllers, Room unit CLC & RAD Chilled ceiling and radiator applications...
  • Page 3 DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™ RXB (KNX) Technical manual Version 2.37 and higher DESIGO™...
  • Page 5 Tab 07 FNC – Fancoil applications Description of functions for FC-10, FC-11, FC-12 CM110385 Applications from FC-10, FC-11, FC-12 CM110672 Tab 08 DESIGO RXB / RXL Installation guide CM110381 Siemens Technical manual DESIGO RXB (KNX) CM110389de01_05 Building Technologies Contents 28.02.2009...
  • Page 7 Building Automation DESIGO™ ORKS RXC, RXB, RXL, RXA Room automation systems Proprietary Communications Selection guide Non-communicating Flexibility...
  • Page 8 Communication KNX / EIB ORKS standard standard Room controllers and devices devices accessories from Siemens or third-party manufacturers Identical range of functions in the RAD, CLC, FNC, VAV, FPB applications QAX... Identical room units Principal features The four ranges, RXC, RXB, RXL, and RXA are tailored to the various bus systems...
  • Page 9 Product scope Communication KNX / EIB Proprietary Applications (HVAC functions) and suitable RAD, CLC, FNC, VAV, RAD, CLC,FNC RAD, CLC,FNC controllers FPB, INT (downloadable) (selected via tool) (selected via tool) (selected via (see page 4 for details) DIP switch) Room units for HVAC operation Electrical controls (lighting, blinds) Conventional switches EIB third-party devices...
  • Page 10 Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 © 2000 - 2009 Siemens Switzerland Ltd CA110331en_03 4 / 4 www.buildingtechnologies.siemens.com Subject to change 31 Jan 2009...
  • Page 11 Building Automation RXB room automation system System overview...
  • Page 13: Table Of Contents

    Contents Comfort and well-being in every room ................ 5 Range overview ......................6 Coordinated room controllers ..................7 The room units: the key to individual comfort ............8 Applications ......................... 10 Installation........................11 Engineering and commissioning ................12 Integration into building automation and control systems ........15 RXB overview.......................
  • Page 15: Comfort And Well-Being In Every Room

    Comfort and well-being in every room Most people in the industrial world spend 90 % of their time indoors. About one third of this time is spent at work. In this context it is clear that good indoor air quality, the right room temperature and draught- free air renewal are vital prerequisites for motivation and a sense of well-being.
  • Page 16: Range Overview

    "application") comprising a set of HVAC applications. The application actually required is enabled in the commissioning phase. The Building Automation section of Siemens Building Technologies holds a library of applications, which is continuously being expanded (see Overview, page 10). For the engineering and commissioning of a network of RXB controllers, use is made of...
  • Page 17: Coordinated Room Controllers

    Coordinated room controllers RXB21.1 and RXB22.1 compact room controllers for fan-coil units The input/output configuration and mounting options of these room controller s makes them ideal for fan coil applications. They can be installed in fan coil units, in control panels or on ducting.
  • Page 18: The Room Units: The Key To Individual Comfort

    The room units: the key to individual comfort The room units of the RXB range cover the widely varying requirements of individual room occupants. When designing these stylish room units, the designers also paid special attention to ergonomic factors. The HVAC system, lighting and blinds can be operated in various ways: •...
  • Page 19 Functions of the room units QAX... 30.1 31.1 32.1 33.1 34.1 34.3 39.1 84.1 90.1 91.1 Built-in room temperature sensor Room temperature setpoint adjustment Selection of operating mode ( /Auto) Selection of operating mode ( /Auto) and fan speed LCD display for room temperature, operating mode and fan speed PPS2 interface to RXB room controller...
  • Page 20: Applications

    Applications The scope of the RXB controllers is defined by the pre-programmed application modules. The following is an overview of the various applications and associated controllers. The controllers are shipped from the factory pre-programmed with a set of applications. The required application is then enabled with a tool (ETS3, ACS or the "HandyTool"). Due to the fact that the applications are largely pre-defined, engineering simply involves the definition of a small number of parameters, e.g.: •...
  • Page 21: Installation

    Installation The RXB controllers are designed for various types of installation (mounted with screws or on DIN rail): • In fan coil units • In control panels • In ceiling voids • Under floors • In sill or floor ducting. 01654 Various options for installation Terminal covers are required when mounting the controllers outside control panels or...
  • Page 22: Engineering And Commissioning

    Engineering and commissioning The RXB controllers can be operated either as stand-alone controllers or in conjunction with a building automation and control system. They are commissioned with one of the following tools, depending on their intended function: – ETS3 Professional –...
  • Page 23 Parameter setting For details, please refer to documents CM110384 and CM110385. Communications links For the integration in building automation and control systems, communications links are created by use of group addresses (ETS3).
  • Page 24 Addressing Every device must have its own physical address. Addresses can be assigned with one of the three tools. Options for connecting the tools Building autometion interface PPS2 PPS2 1. ETS3 or ACS connected to standard room unit *) 2. ETS3 or ACS connected to RXB controller *) 3.
  • Page 25: Integration Into Building Automation And Control Systems

    Integration into building automation and control systems BACnet PX KNX 1 PX KNX 2 OCI700 KNX / EIB Backbone Area coupler 2.0.0 KNX Area 2 Line coupler Line coupler 2.3.0 2.7.0 RMH... RMU... RMB795 Bus supply Bus supply Room Room Room supply controllers...
  • Page 26 Integration into the management level Depending on the degree of complexity required, a management station incorporates the following program modules for the user: • Graphics-based operation of the site (plant graphics) • Time schedules for a wide range of switching routines •...
  • Page 27 Central and local control of operating mode The diagram below shows an example of how the central time schedules (Building use and Room occupancy) interact with the local /Auto control on the room unit (operating as an occupancy function in this case). It is also possible to use a presence detector for local control.
  • Page 28: Rxb Overview

    RXB overview RXB room controllers Document RXB21.1, Room controller for fan-coil units CM2N3873 RXB22.1 RXB24.1 Room controllers for chilled ceilings and radiators CM2N3874 RXB room units QAX30.1 Room unit with temperature sensor CA2N1741 QAX31.1 Room unit with temperature sensor and setpoint adjuster CA2N1741 QAX32.1 Room unit with temperature sensor, setpoint adjuster and...
  • Page 30 Siemens Schweiz AG Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.siemens.com/sbt Building Automation Subject to technical change CM110380en_02 • 30.11.2007...
  • Page 31 DESIGO™ Hardware overview RX Integration Room controllers Room units Field devices Engineering Accessories Integration Engineering Room controllers Room units Field devices Accessories 1/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 32 Room controllers for fan coil systems, chilled ceilings and radiators CA2N3881 RXA29.1 Room controller for fan coil systems CA2N3882 DESIGO RXB room controllers with EIB bus communications RXB10.1 Room controller in room-style housing for CLC, RAD and VAV systems, supply or extract air (EIB) CA2N3870 RXB21.1...
  • Page 33 Room unit with temperature sensor (without PPS2, for RXA) CM1N1721 QAA27 Room unit with temperature sensor and setpoint adjustment (without PPS2, for RXA) CM1N1721 BSGN-U1 Universal setpoint adjuster (without PPS2, for RXA) CA1N1985 3/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 34 As QBM65-.../C, output signal 4 … 20 mA QBM81-... CA1N1552 Differential pressure switch QBM62.1.. (Replaced) CM1N1913 Differential pressure sensor with extracting-the-root characteristic QBM62.2.. (Replaced) CM1N1914 Differential pressure sensor with linear characteristic 4/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 35 Fixed combination valve + actuator 2W.., 4W.., 5W.. Fixed combination CE1N4846 X Preferred solution o Admitted solution (eventually with restrictions) consider only if X is not feasible. Details see table "Suitable valve actuators" 5/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 36 M30 x 1.5 VMP43... Small valves CM1N4841 X Preferred solution o Admitted solution (eventually with restrictions) consider only if X is not feasible. Details see table "Suitable valve actuators" 6/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 37 Technical manual and applications library RXL for CC-02, FC-10, FC-11, FC-12 CM110789 Applications library RXC V1 CA1Z3810 Applications library RXC V2 CA110300 Planning and installation manual RXC V1 CA1Z3800 Planning and installation manual RXC V2 CA110330 7/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 38 STP71 STP72E 3rd party thermic SQS81 SSA81 SSB81 SSD81 SSC81 SSP81 3rd party motoric Key: Discontinued Default in tool Selectable in tool Not selectable in tool select 3rd party motoric 8/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 39 (RXA: Only thermic or motoric can be set by means of DIP switches) Selectable in tools (RXA: Only thermic or motoric can be set by means of DIP switches) Not selectable in tools select 3rd party motoric 9/10 Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 40 + AL100 Push 160 N SSP51KNX + AL100 Push / Pull Set actuator to Set actuator PULL! to PUSH! 120 N SQS81... (Alt) 10/10 © 1998 - 2009 Siemens Switzerland Ltd. Siemens Hardware overview RX CA2N3804en_06 Building Technologies 25 May 2009...
  • Page 41 RXB21.1 Room controllers RXB22.1 For fan-coil applications FC-10, FC-11, FC12 with Konnex bus communications (S-mode and LTE mode) The RXB21.1 and RXB22.1 room controllers are used for temperature control in individual rooms.  For 2-pipe or 4-pipe fan-coil systems, with or without change-over ...
  • Page 42 For details, refer to the FNC description of functions, document CA110385. When DESIGO RXB controllers are integrated into a building automation and control system, or into a Synco system, additional functions become available such as time scheduling, central control of setpoints, etc.
  • Page 43  internal relay for electric heating one 3-position actuator coil RXZ20.1 Accessories: Terminal covers Ordering When ordering please specify the quantity, product name, type code and application group. Example: Room controllers, type RXB21.1/FC-10 3/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 44 Compatibility The RXB2… room controller is compatible with field devices from Siemens Building Technologies and with KNX / EIB-compatible third-party devices. For details, refer to the DESIGO RX hardware overview, CA2N3804. Design The RXB2... controllers consist of a housing base, a housing cover and the printed circuit board with connection terminals.
  • Page 45 The conductors must be secured with cable ties (see diagram). Ensure that the power is off before inserting or Warning! removing plug-in terminals connected to a mains voltage. 5/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 46 HandyTool QAX34.3  The tool socket is a proprietary socket. Notes A Siemens connecting cable must be used (e.g. PXA-C1). When connected to Ethernet, the device on the other end may be damaged! Caution!  The tools ETS3 and ACS, even if connected to a tool socket, require an interface: ...
  • Page 47 This is acceptable because the two sequences never operate at the same time. With low loads (< 2VA) the voltage tolerance may be greater than +20% (see technical data). 7/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 48 Function test A special test mode (ETS3 Professional or "HandyTool") is available for operation of the outputs. Further, if the digital inputs have been activated, they can be interrogated. 8/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 49 Inductive load L/R Max. 7 ms Relay type Monostable Contact rating with AC voltage Max. admissible load (resistive only) Max. 1.8 kW External fuse (essential) Max. 10 A 9/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 50 Building Services Management Manual – Fundamental principles, and ... – Applications Zentralverband Elektrotechnik- und Elektronikindustrie e.V. (ZVEH) (Central association for the electrical and electronic engineering industry), Stresemannallee 19D-60596 Frankfurt a. M, Germany. 10/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies...
  • Page 51 1 2 3 4 5 6 7 8 2 KNX / EIB data cable (CE–) 6 RxD 3 Not used 7 PPS2 (CP+) / TxD 4 Not used 8 PPS2 (CP–) 11/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 52 1 2 3 4 5 6 7 8 2 KNX / EIB data cable (CE–) 6 RxD 3 Not used 7 PPS2 (CP+) / TxD 4 Not used 8 PPS2 (CP–) 12/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 53 For information on the compatibility of field devices with the RXB21.1 and RXB22.1 Note room controller, refer to the various application descriptions (see the FNC description of functions, document CA110385) 13/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 54 (max. 2 STA72E / STP72E actuators per Y1 output on the UA1T) Notes – The UA1T requires an AC 24 V supply voltage – The UA1T is not suitable for the connection of 3-position actuators. 14/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 55 Dimensions Dimensions in mm Without terminal cover 51,5 With terminal covers 112,4 107,8 15/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 56 Drilling diagram (1:1) 43,2 86,3  2006 - 2010 Siemens Switzerland Ltd. Subject to alteration 16/16 Siemens RXB21.1, RXB22.1 Room controllers CM2N3873en_06 Building Technologies 02 Apr 2010...
  • Page 57 RXB24.1 Room controller For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode) The RXB24.1 room controller is used for temperature control in individual rooms.  For chilled ceiling and radiator systems  PI control ...
  • Page 58 For details, refer to the CLC and RAD description of functions, document CA110384. When DESIGO RXB controllers are integrated into a building automation and control system, or into a Synco system, additional functions become available such as time scheduling, central control of setpoints, etc.
  • Page 59 Example: Room controllers, type RXB24.1/CC-02 Compatibility The RXB24.1 room controller is compatible with field devices from Siemens Building Technologies and with KNX / EIB-compatible third-party devices. For details, refer to the DESIGO RX hardware overview, CA2N3804. Design The RXB24.1 controller consists of a housing base, a housing cover and the printed circuit board with connection terminals.
  • Page 60 The cable is connected to the room controller by breaking out the perforated cable entry guide. Removing the terminal cover 4 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 61  KNX / EIB bus (terminals CE+ and CE-) for communication with:  PX/KNX interface (to DESIGO INSIGHT)  Interface OCI700 (to Synco)  Other DESIGO RXB controllers  KNX / EIB compatible field devices (e.g. temperature sensor) 5 / 16 Siemens RXB24.1 – Room controller...
  • Page 62 HandyTool QAX34.3 HandyTool QAX34.3  The tool socket is a proprietary socket. Notes A Siemens connecting cable must be used (e.g. PXA-C1). When connected to Ethernet, the device on the other end may be Caution! damaged!  The tools ETS3 and ACS, even if connected to a tool socket, require an interface: ...
  • Page 63 This is acceptable because the two sequences never operate at the same time. With low loads (< 2VA) the voltage tolerance may be greater than +20% (see technical data). 7 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies...
  • Page 64 "Appl." and "Loc" in the commissioning stage. Function test A special test mode (ETS3 Professional and HandyTool) is available for operation of the outputs and interrogation of the inputs. 8 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 65 KNX / EIB (electrically isolated) Transceiver TP-UART 5 mA Bus current Baud rate 9.6 kbit/s Bus topology Refer to KNX / EIB manual (Reference documentation, see next page) 9 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 66  Building Services Management Manual – Applications Zentralverband Elektrotechnik- und Elektronikindustrie e.V. (ZVEH) (Central association for the electrical and electronic engineering industry) Stresemannallee 19D-60596 Frankfurt a. M, Germany. 10 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 67 1 2 3 4 5 6 7 8 2 KNX / EIB data cable (CE–) 6 RxD 3 Not used 7 PPS2 (CP+) / TxD 4 Not used 8 PPS2 (CP–) 11 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 68 For information on the compatibility of field devices with the RXB24.1 room controller, refer to the various application descriptions (see the CLC and RAD description of functions, document CA110384) 12 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies...
  • Page 69 (max. 2 STA72E/STP72E actuators per Y1 output on the UA1T) Notes – The UA1T requires an AC 24 V supply voltage – The UA1T is not suitable for the connection of 3-position actuators. 13 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 70 Dimensions Dimensions in mm Without terminal cover 51,5 With terminal covers 112,4 107,8 14 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 71 Drilling diagram (1:1) 43,2 86,3 15 / 16 Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 72 16 / 16  2007 - 2010 Siemens Switzerland Ltd. Subject to change Siemens RXB24.1 – Room controller CM2N3874en_04 Building Technologies 02 Apr 2010...
  • Page 73 DESIGO RX QAX34.3 Room unit with PPS2 interface For use with: – Equipment from the RXC, RXB, RXL and RXA (PPS2) ranges – DESIGO PX automation stations – Devices with a PPS2 interface  Measurement of the room temperature  Bias switch for adjustment of the room temperature setpoint ...
  • Page 74 LCD panel. The housing and mounting plate are plastic. Opening the housing Index and manufacturing date Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
  • Page 75 Economy operating mode Automatic fan control Comfort operating mode Automatic fan control Comfort operating mode Manual fan control, fan speed 1 Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
  • Page 76 Until the controller recognizes the room unit as a PPS2 by controller user, the display reads: Ready for 1 s after recognition by the controller, the room unit is ready for operation operation Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
  • Page 77 If the room unit is connected to a room controller in the DESIGO RXB, RXL or RXC Displaying the “Wink” function of KNX/EIB range, the display can be used as an aid to commissioning. If the commissioning tool and L...
  • Page 78 Solid or stranded conductors 0.8 … 2.5 mm Single cable length between controller See installation guides: and room unit DESIGO RXC: CA110334, DESIGO RXB & RXL: CM110381 DESIGO RXA: CA2Z3884 DESIGO PX: CA110396 Cable type 2-core, twisted pair, unscreened Housing protection...
  • Page 79 PPS2 interface, power supply Device power supply, PPS2 data (positive) CP– Device power supply, PPS2 data (negative) Wiring diagram The example below shows the room unit connected to a DESIGO RXB room controller. PPS2 = Twisted pair QAX34.3 room unit RXB… room controller Siemens QAX34.3 –...
  • Page 80 Dimensions Dimensions in mm 23,8 89,45  2006 - 2009 Siemens Switzerland Ltd. Subject to change Siemens QAX34.3 – Room unit with PPS2 interface CM2N1640en_04 Building Technologies 30 Jun 2009...
  • Page 81 CLC and RAD description of functions for CC-02 (CLC and RAD applications: see document CM110671). Related documents CM1Y9775 RXB integration, S-mode. CM1Y9776 RXB / RXL integration – Individual addressing. CM1Y9777 Third-party integration. CM1Y9779 Working with ETS. CM110384en_03 Siemens Building Technologies 28 Feb 2009...
  • Page 82 Local control of room operating mode via the Temporary Comfort mode input ......................51 5.4.7 Effective room operating mode ..............52 2/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Contents 28 Feb 2009...
  • Page 83 Window switch (LTE mode) ................ 98 9.2.2 Presence detector (LTE mode)..............98 9.2.3 Dewpoint sensor (LTE mode) ..............98 Peripheral functions ..................99 3/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Contents 28 Feb 2009...
  • Page 84 Case 6: Separate display, separate schedules .........137 14.7 Case 7: Separate display, shared Synco schedule........138 Working with different tools..............139 4/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Contents 28 Feb 2009...
  • Page 85: Introduction

    First edition Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. Quality assurance These documents have been prepared with great care.
  • Page 86: Document Use / Request To The Reader

    Swiss headquarters. E-mail: fieldsupport-zug.ch.sbt@siemens.com. Please note that without prejudice to your statutory rights, Siemens accepts no liability for any losses resulting from non-observance or improper observance of the points referred to above.
  • Page 87: Bus Supply For Rxb Konnex Controllers

    We recommend the following products: Manufacturer Type Designation Siemens Building Technologies ACX95.320/ALG Power supply 320 mA Siemens Automation and Drives 5WG1 125-1AB01 Power supply 160 mA 5WG1 125-1AB11 Power supply 320 mA 5WG1 125-1AB21 Power supply 640 mA RXB Konnex controller communications The RXB Konnex controllers support communications as defined in the Konnex specification.
  • Page 88: Lte Mode

    • Outside temperature zones. • Heat distribution zones. • Refrigeration distribution zones. For further details, refer to the Konnex specification. 8/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Introduction 28 Feb 2009...
  • Page 89: Definitions / Tools

    A list of all S-mode communication objects is located in section 12.5; see a detailed description of the Konnex data types in section 12.10. 9/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 90 All communication objects operating in LTE mode are described as follows: communication objects Possible partner function Known partner devices blocks HVACMode 110 HVACS Siemens: HVAC-Mode Scheduler Synco RM700 TimeswitchZone 2) 104 PMC Program to HVAC-Mode Conversion The name of the LTE communication object is entered here.
  • Page 91: Supported Tools

    Refer to the EIB manual for more details. Open the project and select a device. To start parameterization, select Edit, Edit parameters. 11/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
  • Page 92: Parameterization Using Acs

    This information can be found in the ACS description. In the ACS Service program, select Plant, Open to open the plant. To start parameterization, select Applications, Parameter settings: 12/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 93: Parameterization Using The Handytool

    Major parameterization. – All parameters. Parameters The parameter numbers and their functions are described in the sections below. 13/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools 28 Feb 2009...
  • Page 94: Operating Handytool Functions

    The numbers of the parameters are listed in sections 12.7 and 12.8, and in the descriptions of the functions. A table of parameters with enumerations fort he HandyTool is shown in Section 12.9. 14/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 95 P033 Comfort cooling setpoint. P034 Comfort heating setpoint. P035 Precomfort heating setpoint. P036 Economy heating setpoint. P240 Device status. 15/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools 28 Feb 2009...
  • Page 96: Major Parameterization Using Room Unit Qax34.3

    *002 can assume the values 0 … 15. *003 can assume the values 1 … 255. Example: 0.2.27 Each address must be unique within a plant. 16/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
  • Page 97: Upload/Download Parameters Using Room Unit Qax34.3

    • If the parameter set matches the connected controller, start download (display flashes). • If connected successfully, "P1" is displayed (see 2.5.2). 17/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
  • Page 98: Test The Periphery Using Room Unit Qax34.3

    % entry. – Motorized actuators open at 100% 1.5 times the runtime, and close at 0% 1.5 times the runtime. 18/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Definitions / Tools...
  • Page 99 To exit test mode, press >- (Escape) 2 - 3 times (depending on the situation). If no further button is pressed for 5 minutes, the controller automatically reassumes Normal mode and all physical outputs are switched back. 19/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 100: Select Communications Mode

    It can be used for operation in – S-mode. – LTE-mode and S-mode. The send heartbeat and receive timeout are described in section 10.1. 20/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode...
  • Page 101: Address Zones In Lte Mode (Together With Synco)

    Synco device to process the Zone = ---, 1...31 information (e.g. RMU7xx or RMB7xx). 21/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode 28 Feb 2009...
  • Page 102 See also "Master/slave", page 94. Select the menu option Communication. ETS3 Professional 22/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode 28 Feb 2009...
  • Page 103 • If the geogr zone or a TS zone has value = -1 for one of the three values, the entire zone is out of service. 23/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03...
  • Page 104: Rxb Application Example With Rmb795 For Geographical And Time Switch Zones

    G: 2.2.1 G: 3.7.1 G: 2.1.1 D = Device address, G = Geographical zone (Apartment . Room . Subzone). 24/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode 28 Feb 2009...
  • Page 105 Settings on the control The RMB795 control unit only allows for setting the room group, i.e. the geographical unit zone (apartment). 25/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode...
  • Page 106 Each KNX member requires an individual device address, entered in the floor plan above with D:11x. The device address in our example was assigned based on the bus topology. 26/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 107: Implement Application Example

    Implementation upon Upon commissioning, enter the settings for the same-name data points in the devices commissioning according to the created list. 27/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Select communications mode...
  • Page 108: Heating And Refrigeration Demand Zones

    CLC and RAD applications. • If not 2-pipe fan coil is selected, heating and refrigeration demand is sent simultaneously to generation. 28/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 109: Applications / Parameters

    Alternatively: _Select View, Open Catalog . Select one or several devices, copy them and insert them in the line. Select the application under Commissioning . ACS Service 29/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Applications / Parameters...
  • Page 110: Parameter Settings

    The following sections describe how to set parameters, with only slight differences between the two PC tools. The display is the main difference. 30/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 111: Room Operating Modes

    Room operating modes Description The operating modes in DESIGO RXB are Comfort, Precomfort, Economy and Protection. In addition, the controller has a frost Protection limit, at which an alarm can be triggered. Each room operating mode has separately adjustable heating and cooling sequence setpoints.
  • Page 112: Overview

    Overview 32/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 113: Determine The Room Operating Mode With Desigo (S-Mode)

    The key point in time is the moment at which the state changes (edge). If another source of third priority later changes the state, the last known change is valid . 33/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 114: Local Control Of Room Operating Mode Via A Window Contact

    R W C T U 0 1 1 0 0 1.019 0 = Closed DPT_WindowDoor 1 = Open 34/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 115: Central Control Of Room Operating Mode Via Input From The Use Schedule

    • Priority 3 influences are disabled (schedule occupancy, presence detector, room unit, and Temporary Comfort mode). • Application: Extended building vacancy. 35/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
  • Page 116: Central And Local Control Of Room Operating Mode Based On Occupancy

    It controls the room operating mode of a room controller while the building is in use. Outside the building-in-use period, it is disabled. 36/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 117 R W C T U 0 1 1 0 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 37/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 118 In the case of integration into a building automation and control system, the data is mapped to the following output communication object: PPS2 38/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
  • Page 119: Local Control Of Room Operating Mode With A Room Unit

    • The Effective occupancy or Temporary Comfort mode (both priority 3) can cause the Effective room operating mode to change again last command wins. 39/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 120: Local Control Of Room Operating Mode Via The Temporary Comfort Mode Input

    R W C T U 0 1 1 0 0 1.017 1 = Trigger DPT_Trigger 0 = Not used 40/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 121: Effective Room Operating Mode

    1 0 1 1 0 20.102 1 = Comfort DPT_HVACMode 2 = Precomfort 3 = Economy 4 = Protection 41/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 122: Desigo Examples

    12.00 and 13.00 ( standby ). • In Room 3, the window is opened briefly once in the morning and once at night (1). 42/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03...
  • Page 123 • Room 2 is occupied in the evening beyond the building-in-use period (4). However, at the end of the building-in-use period, the room operating mode still changes to Economy. An alarm can be triggered if required. 43/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 124 Protection Presence detector Room 2 Occupied Unoccupied Effective room operating mode Comfort Room 2 Precomfort Economy Protection 44/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 125: Determine The Room Operating Mode With Third-Party Products (S-Mode)

    The key point in time is the moment at which the state changes (edge). If another source of third priority later changes the state, the last known change is valid . 45/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 126: Local Control Of Room Operating Mode Via Window Contact Input

    R W C T U 0 1 1 0 0 1.019 0 = Closed DPT_WindowDoor 1 = Open 46/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 127: Central Control Of Room Operating Mode With An Input From The Room Operating Mode Schedule

    • The Protection room operating mode has priority 1, i.e. presence detector and room units are disabled. 47/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 128: Central Control Of The Room Operating Mode Via The Schedules Use And Occupancy

    (see page 102); alternatively an EIB/KNX presence detector connected to the EIB/KNX bus may be used (see diagram below). The two inputs are OR-linked: If one signals presence, presence applies. 48/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 129 R W C T U 1 0 1 1 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 49/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 130: Local Control Of Room Operating Mode With A Room Unit

    Auto means: "changes to Auto ". 1) Comfort mode is active for the predefined Temporary Comfort period (see page 103). The room controller then returns to Economy. 50/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 131: Local Control Of Room Operating Mode Via The Temporary Comfort Mode Input

    • The Effective occupancy or the room unit (both priority 3) can cause the Effective room operating mode to change again last command wins. 51/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 132 R W C T U 1 0 1 1 0 1.001 0 = Off DPT_Switch 1 = On 52/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 133: Third-Party (S-Mode) Examples

    Comfort room operating mode is then initiated locally via the room unit (room 1) or presence detector (room 2). 53/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 134 Room without room unit Occupied Presence detector Unoccupied Room 2 Comfort Effective room Precomfort operating mode Room 2 Economy Protection 54/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 135: Determine The Room Operating Mode With Synco (Lte Mode)

    The key point in time is the moment at which the state changes (edge). If another source of third priority later changes the state, the last known change is valid . 55/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 136: Local Control Of Room Operating Mode Via Window Contact Input

    However, the room controller can be used to force enabling of priority 3 influences via local Comfort mode by ignoring enable Comfort . PPS2 56/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
  • Page 137: Central Control Of Room Operating Mode Via Room Operating Mode Input

    The following LTE-mode communication object is provided for central control: K N X Enable Comfort (input) Possible partner function blocks) Known partner devices EnableComfort 110 HVACS Siemens: HVAC-Mode Scheduler Synco RMB795 Timeswitch zone 104 PMC Programs to HVAC-Mode Conversion Possible states are:...
  • Page 138: Local Control Of Room Operating Mode Via Presence Detector

    (people leave room) Precomfort Economy if room operating mode = Economy Key: Occupied means: "changes to occupied ". 58/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 139: Local Control Of Room Operating Mode With A Room Unit

    Auto means: "changes to Auto ". 1) Comfort mode is active for the predefined Temporary Comfort period (see page 103). The room controller then returns to Economy. 59/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 140: Lte Mode Examples

    Comfort room operating mode is then initiated locally via the room unit (room 1) or presence detector (room 2). 60/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 141 Occupied Presence Unoccupied detector Room 2 Comfort Precomfort Effective room operating mode Economy Room 2 Protection 61/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 142: Determine The Room Operating Mode Without A Bus (Stand-Alone)

    If there is no bus connection, the controller assumes the following defaults: • Use = Building in use. • Occupancy = Occupied. 62/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
  • Page 143: Local Control Of Room Operating Mode Via A Window Contact Input

    PPS2 The presence detector is connected directly to a digital input of the room controller (see page 102). 63/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 144: Local Control Of Room Operating Mode With Room Unit

    The table below shows the effect of the /Auto button on the Effective room operating mode of the room controller. 64/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes...
  • Page 145: Example For Stand-Alone

    Comfort (2); when the window is opened (3), after timer expiration (4), or after pressing again the /Auto button (5), the room operating mode returns to Economy . 65/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 146 / Auto button Auto on room unit Room 3 Comfort Effective room operating mode Room 3 Precomfort Economy Protection. 66/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room operating modes 28 Feb 2009...
  • Page 147: Setpoint Calculation

    8 present setpoints Frost setpoint (6.1.1) Effective PPS2 room operating mode Effective heating setpoint SpH (6.1.2) Effective cooling setpoint SpC 67/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 148: Bus Output For Current Setpoints

    Bus outputs LTE mode In LTE mode, the current and effective setpoints are not transmitted to the building automation and control system. 68/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation...
  • Page 149: Setpoint Settings With The Tool

    Select the Room Temperature Setpoints tab. ETS3 Professional ACS Service The setpoints can be modified under Room temp setpoints : 69/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 150: Setpoint Setting Runtime

    0 1 1 0 0 222.100 3 floating point values - Comfort (°C) DPT_TempRoomSetp - Precomfort (°C) SetF16[3] - Economy (°C) 70/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 151: Central Setpoint Shift

    Setpoints heating (input) Setpoints cooling (input) Possible partner Known partner devices function blocks) Siemens: TempRoomSetpSetHeat Siemens SBT proprietary Synco RMB795 TempRoomSetpSetCool Geographical zone Important! Setpoints changed by a tool (e.g. HandyTool) are overwritten by PX-KNX during room STOP controller startup!
  • Page 152: Local Setpoint Shift

    LTE-mode, the central setpoint shift is transmitted via the following communication objects (triplets): Setpoint shift heating (input) Setpoint shift cooling (input) Possible partner Known partner devices function blocks) Siemens: TempRoomSetpSetHeatShift 115 HVACOPT Synco RMB795 TempRoomSetpSetCoolShift HVAC Optimizer Geographical zone Local setpoint shift If setpoints are shifted locally and corrected by the controller, local shift is applied.
  • Page 153 Send heartbeat Value R W C T U 1 0 1 1 0 9.002 Floating point (K) DPT_Value_Tempd 73/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 154: Temperature Measurement

    No sensor No sensor connected. Only measured value Uses the signal, see "analog input B1", page 112. acquisition 74/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Temperature measurement 28 Feb 2009...
  • Page 155: Averaging Analog Input & Pps2 Interface

    7.1.4 Sensor correction The value of the local sensors (PPS2 and B1) can be corrected in the tools (see page 115). 75/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Temperature measurement...
  • Page 156: Temperature Sensor Outputs On The Konnex Bus

    In LTE mode, the room air temperature from directly connected sensors is mapped as follows: Room temperature output (output) Possible partner function Known partner devices blocks) TempRoom 390 UHD Siemens: UserHVACDisplay Synco RMH760 / RMB795 RMU710 / 20 / 30 Geographical zone 76/140 Siemens...
  • Page 157: Temperature Sensor Input From Konnex Bus

    For a Konnex sensor the send heartbeat must be set to "Cyclical sending enabled" Note! STOP Room temperature (input) Possible partner function blocks) Known partner devices TempRoom 321 RTS Siemens: Room Temperature Sensor Synco RMH760 Geographical zone RMU710 / 20 / 30 QAW740 77/140 Siemens...
  • Page 158: Outside Air Temperature Via Konnex Bus (Clc02, Rad01)

    In LTE mode, the outside temperature is sent in a zone intended specifically for that purpose. Outside temperature input (input) Possible partner function blocks) Known partner devices TempOutside 320 OTS Siemens: Room Temperature Sensor Synco RMH760 Outside temperature RMU710 / 20 / 30 zone RMB795 / RMS705...
  • Page 159: Control Sequences

    The table below shows the possible combinations: Actuator Controller Outputs required type Thermal RXB24.1 Motorized RXB24.1 Electro- RXB24.1 mechanic (ON / OFF) 79/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
  • Page 160 Parameterization The actuator type used must be defined at the engineering stage: Select Edit parameters, Sequences : ETS3 Professional 80/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
  • Page 161 This is especially important for fast running actuators. For electromechanic actuators, the actuator running time can be adapted. For fast actuators , select valve type "Motoric 3rd party devices ". 81/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 162 Running time heat surf valve 150 s 0 ... 360 s *064 Offset heating surface valve 0 ... 360 s *066 82/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
  • Page 163: Values Representing Radiator Valve Actuator Positions

    ETS3 Professional Note The two fields at the bottom appear only if "LTE and S-mode" is selected in the Communication menu. 83/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
  • Page 164: Valve Exercising Feature

    To override the radiator valve actuator, the test mode must be activated via the Note communication object Application mode (see page 105). 84/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
  • Page 165: Downdraft Compensation

    1600 seconds "OPEN" (1s On, 1 s Off) 400 s "CLOSE" (1s On, 19 s Off) The long cycle time ensures that the valves are fully opened and closed. In a network containing several room controllers, the opening of the Siemens thermic actuators is staggered to prevent the heating load from fluctuating.
  • Page 166 *080 Enable the function The following conditions must be fulfilled: – The room controller must be in Comfort room operating mode. 86/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
  • Page 167: Chilled Ceiling (Clc01)

    (5% – 1 sec ON / 19 sec OFF). Then thus also receive pulses from the controller when closed. 87/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 168: Values Representing Chilled Ceiling Valve Actuator Positions

    Cooling surface output (output) Possible partner function blocks Known partner devices ActPosSetpCoolStageA 352 HVA HVAC Valve Actuator Geographical zone 88/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
  • Page 169 The two fields at the bottom only are shown if "LTE and S-mode" are selected in the Communication menu. ACS Service Select menu item Sequences : 89/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences...
  • Page 170: Valve Exercising Feature

    The example below shows central dewpoint monitoring combined with passive dewpoint monitoring provided by the DESIGO RXB controller. The flow temperature is increased in accordance with a centrally calculated dewpoint temperature. If the dewpoint temperature in the room exceeds the flow temperature, condensation forms and the cooling valve closes.
  • Page 171: Central/Passive Dewpoint Monitoring

    R W C T U 1 0 1 1 0 1.005 0 = No alarm 1 = Alarm (condensation) DPT_Alarm 91/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
  • Page 172: Chilled Ceiling And Radiator 4-Pipe (Clc02)

    • For CLC02, no electromechanic actuators are permitted due to load. (FNC: 10, 12, Notes • Also, thermal valves cannot run parallel operation of Y1 / Y2 and Y3 / Y4. 92/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 173: Override The Valve Actuator

    Heating and cooling alternately, with the heating value. Motorized actuators: Heating and cooling valve driven to the heating position. 93/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Control sequences 28 Feb 2009...
  • Page 174: Master/Slave

    The slave controller is controlled by a master controller via the KNX bus. The master and slave controllers operate in parallel. The room temperature is measured only by the master. 94/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 175: S-Mode

    Note You need 4 group addresses (GA1 … GA4) regardless of the number of slaves. Select Master/Slave: ETS3 Professional 95/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Master/slave 28 Feb 2009...
  • Page 176: Window Switch (S-Mode)

    This binding ensures that both controllers react when a dewpoint sensor becomes active. If several slaves are equipped with dewpoint sensors, the correct evaluation is required for the logic block. 96/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 177: Lte Mode With Zones

    Geogr. zone and M/S zone do not necessarily need to match. In reality, however, it makes sense as seeing which slave belongs to which master is obvious immediately. ACS Service Select Master/Slave: 97/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Master/slave...
  • Page 178: Window Switch (Lte Mode)

    For master/slave mode, only the master's presence detector is evaluated without special measures, which also influences the slave controllers. Window switches on the slaves are NOT considered. 98/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 179: Peripheral Functions

    Master Slave RXB... RXB... units with buttons for setpoint shift. Auto QAX33.1 QAX34.1 99/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Master/slave 28 Feb 2009...
  • Page 180: General / Central Functions

    Communication or General functions or Central functions . See Section 10.1 10.2 7.1.2 10.3 10.4 10.6 10.8 10.14 100/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
  • Page 181 HandyTool General and central functions are set using parameters 117 – 137 (see the individual sections for detailed information). 101/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
  • Page 182: Send Heartbeat And Receive Timeout

    Do not connect the same type of sensor / functions to both digital inputs. Note The controller would ignore the second input. 102/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
  • Page 183: Temporary Comfort Mode

    Basic setting *131, *132 0 = Disabled/ Off 0 = Disabled 1 = Enabled / On 103/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
  • Page 184: Heating/Cooling Signal Output

    In LTE mode, the energy demand is determined by two signals: Heat demand heating surface (output) Possible partner function blocks Known partner devices EnergyDemRD 153 RHDTTU Siemens: Radiator Energy Demand Synco RMH760 Distribution zone, Transformer TU RMU710 / 20 / 30...
  • Page 185: Special Functions

    *) Exit from Test (7) is only possible with the sequence Off (6) + normal mode (0). The following communication object is used in LTE mode: Application mode (input) Possible partner function blocks Known partner devices ContrMode 104 PMC Siemens: Programs to HVAC-Mode Conversion Synco RMB795 Time switch 109 BOS zone Building/Occ-Mode Source...
  • Page 186: Morning Boost (Morning Warmup, 2)

    Precooling (Precool, 5) This function is used to cool rooms to the Comfort cooling setpoint prior to actual occupancy. Y [%] 106/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
  • Page 187: Test Mode (Test, 7)

    Protection heating setpoint again. When the room temperature rises above the Protection setpoint, the controller reverts to the original application mode (see page 105). 107/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 188: Free Cooling (Freecool, 10)

    (communication object Application mode , see page 105). Terminate function The function is disabled via the building automation and control system. 108/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
  • Page 189: Alarm

    0 1 1 0 0 1.003 Yes (fixed 42 hours) 0 = Disabled / Off DPT_Enable 1 = Enabled / On 109/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
  • Page 190: 10.13.2 Lte Mode

    This ensures that the control station does not miss alarms. K N X AlarmInfo_CS (Output) Possible partner function blocks Known partner devices AlarmInfo_CS Siemens Synco RMU710 / 20 / 30, RMH760, RMB795, RMS705 Broadcast AlarmText_CS (Output) Possible partner function blocks...
  • Page 191: Free Inputs/Outputs

    Free: Bus = 1 = Contact closed Contact closed Contact open Free: Bus = 1 = Contact open Contact open Contact closed 111/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
  • Page 192: 10.15.2 Knx Signals On Digital/Analog Outputs

    Type Send heartbeat States R W C T U 9.001 1 0 1 1 0 DPT_Value_Temp 112/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions 28 Feb 2009...
  • Page 193: Software Version

    Device state *240 Note In Service mode the device state is always = 0 because the application is not running. 113/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies General / central functions...
  • Page 194: Room Unit

    Standard display (only room units with LCD) Room temperature *109 Setpoint display (only room units with LCD) Relative *110 114/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room unit 28 Feb 2009...
  • Page 195 LCD display. Parameter Value HandyTool Temperature unit (Only room units with LCD). *108 Celsius (°C) (basic setting). Fahrenheit (°F) 115/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room unit 28 Feb 2009...
  • Page 196 If "Absolute setpoint shift" is selected, the LCD displays a scale that illustrates the shift as it happens: 10385Z20 Note To reset the setpoint shift, refer to page 116/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Room unit 28 Feb 2009...
  • Page 197: Knx Information

    After switching on the operating voltage, the controller flashes for 3 to 5 seconds in different patterns. If other patterns appear during normal operation, this indicates an error. 117/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information...
  • Page 198: Startup Delay

    • Each group address must have a recipient to acknowledge the telegram, otherwise unwanted repeat-telegrams are generated. • Further notes on reducing bus load, see pages 23 and 83. 118/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 199: S-Mode Communication Objects For Rad/Clc

    Schedule usage 0 1 1 0 0 20.002 DPT_BuildingMode Window switch input 0 1 1 0 0 1.019 DPT_Window_Door 119/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 200: 12.5.2 S-Mode Output Communication Objects

    1 0 1 1 0 C.S. 2 Byte Window switch output 1 0 1 1 0 1.019 DPT_Window_Door 35, 47 120/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 201: Lte-Mode Communication Objects

    – RCCRC Radiator & Chilled Ceiling Room Control – RTS Room Temperature Sensor – ALSrc 1002 Alarm Source 121/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 202: Handytool Parameters By Number

    Running time heat surface valve Offset heating surface valve Outside temp 0% valve pos Outside temp max valve pos Maximum valve pos 122/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 203 Operating system version KNX interface version Device state HandyTool: Visible but not used by the application Handytool: cannot be mapped 123/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 204: Handytool Parameters, Alphabetical

    Master/slave zone (subzone) Max valve position Measured value correction Off-delay occupancy detector Offset cooling surface valve Offset heating surface valve 124/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 205 Time switch zone (room) Time switch zone (subzone) HandyTool: Visible but not used by the application HandyTool: cannot be mapped 125/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 206: Handytool Enumerations

    Rapid ventilation (earlier: air purge) Reset setpoint offset Night purge Application set Application version Operating system version KNX interface version Device state 126/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 207: 12.10 Data Point Type Description

    9 = Fan only 10 = Free Cool 11 = Ice 20 = NoDem 255 = NUL Other: reserved 127/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 208 DPT_TempRoom 3 floating point values (16) (16) (16) SetpSetShiftF16[3] - Comfort (3 x EIS5) - Precomfort - Economy 128/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies KNX information 28 Feb 2009...
  • Page 209: Faq

    ACS : CLC01 shows the lower limit of 21°C for the Comfort cooling setpoint. Answer Setpoint data are only updated when the application (RAD01, CLC01, ...) has been selected. 129/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies 28 Feb 2009...
  • Page 210 The master-controller and slave-controller data is synchronized regularly. If a value changes just after synchronization, it may be a few minutes until it is resynchronized. 130/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03...
  • Page 211 Example: an RXB controller receives the room temperature from a bus sensor. A bus display is used to display the room temperature. The display must get the signal directly from the bus sensor. 131/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 212: Integration Of Rxb In Desigo/Synco

    Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 132/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 213: Case 2: Integration In Desigo

    • Energy demand: to DESIGO. DESIGO INSIGHT PXC... PXC... PX KNX PXM20 Individual addressing Konnex 133/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 214: Case 3: Display In Desigo, With Shared Synco Schedule

    Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 134/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 215: Case 4: Display In Desigo/Synco, With Shared Synco Schedule

    Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 135/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 216: Case 5: Display In Desigo, Separate Schedules

    Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 136/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 217: Case 6: Separate Display, Separate Schedules

    Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 137/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 218: Case 7: Separate Display, Shared Synco Schedule

    Synco Synco Geographical zone Geographical zone Time switch zone Heat demand zone Refrigeration demand zone 138/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Integration of RXB in DESIGO/Synco 28 Feb 2009...
  • Page 219: Working With Different Tools

    An upload is necessary to avoid losing the data from Step 1. The ETS project is missing (no upload possible). The ETS project is NOT updated. 139/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies...
  • Page 220 140/140 Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_03 Building Technologies Working with different tools 28 Feb 2009...
  • Page 221 Related documents CM110384 CLC and RAD functions description for CC-02 CM1Y9775 RXB integration, S-mode. CM1Y9776 RXB / RXL integration – individual addressing. CM1Y9777 Third party integration. CM1Y9779 Working with ETS. CA1N3804 DESIGO RX hardware overview. CM110671en_02 Siemens Building Technologies 14.03.2008...
  • Page 222 2/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 223 Y [%] 70281 Output signal. Room temperature. Effective heating setpoint Heating sequence. Heating valve. TR [°C] 3/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 RAD01 – LTHW radiator...
  • Page 224 Room units. Versions available with temperature sensor, setpoint shift, /Auto switch and LCD display. Compatible controllers. RAD01 runs on RXB24.1/CC-02 4/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 225 Y1 ... Y4: Max. 9.5 VA each (see data sheet 3874). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 5/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 226 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers, type RXB24.1 with application group CC-02.
  • Page 227 Y [%] Output signal. Room temperature. Effective cooling setpoint Cooling sequence. Cooling valve. TR [°C] 7/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC01 – Chilled ceiling...
  • Page 228 Room units. Versions available with temperature sensor, setpoint shift, /Auto switch and LCD display. CLC01 runs on RXB24.1/CC-02. Compatible controllers. 8/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 229 Observe the max. simultaneous load on outputs Y1 ... Y4: Max. 9.5 VA each (see data sheet N3874). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 9/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 230 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. 15 Room controllers, type RXB24.1 with application group CC-02.
  • Page 231 Effective cooling setpoint Heating sequence. Cooling sequence. Heating valve. Cooling valve. TR [°C] 11/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC02 – Chilled ceiling and radiator...
  • Page 232 Room units. Versions available with temperature sensor, setpoint shift, /Auto switch and LCD display. Compatible controllers. CLC02 runs on RXB24.1/CC-02 12/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 233 Identical devices must not be connected to both inputs. Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 13/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008...
  • Page 234 Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 14/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC02 – Chilled ceiling and radiator...
  • Page 235 Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers, type RXB24.1 with application group CC-02. Example RXB24.1/ CC-02 Note The controllers are delivered with the basic settings shown above.
  • Page 236 16/16 Siemens RXB application library (KNX) CM110671en_02 Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008 CLC02 – Chilled ceiling and radiator...
  • Page 237 RXB (KNX) applications library FNC Description of functions for FC-10, FC-11, FC-12 (FNC applications see document CM110672) Supplementary documents CM1Y9775 RXB Integration – S-Mode CM1Y9776 RXB / RXL Integration – Individual Addressing CM1Y9777 3rd Party Integration CM1Y9778 Synco Integration CM1Y9779 Working with ETS CM110385en_05 Building Technologies...
  • Page 238 Local control of room operating mode with a room unit ......41 5.3.6 Local control of room operating mode via the Temporary Comfort mode input ......................42 2/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 239 8.1.3 Heating/cooling output ................84 8.1.4 Actuator type selection ................85 8.1.5 Values representing valve actuator positions ..........89 3/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Contents 28 Feb 2009...
  • Page 240 Heating and cooling demand ..............127 11.6 Heating/cooling signal output ..............128 11.7 Special functions ..................128 11.8 Boost heating (Morning Warmup, 2) ............129 4/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Contents 28 Feb 2009...
  • Page 241 Case 6: Separate display, and separate time schedulers ......163 15.7 Case 7: Separate display, and shared Synco time scheduler ....164 Working with different tools............... 165 5/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 242: Introduction

    • 13.1 Reset and startup response • 13.2 LED flashing pattern • 13.7, 13.8, 13.9 HandyTool parameters with page numbers and enumerations • 14 FAQ 6/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 243: Copyright

    First edition Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. Quality assurance These documents have been prepared with great care.
  • Page 244: Document Use / Request To The Reader

    Swiss headquarters. E-mail: fieldsupport-zug.ch.sbt@siemens.com. Please note that without prejudice to your statutory rights, Siemens accepts no liability for any losses resulting from non-observance or improper observance of the points referred to above.
  • Page 245: Bus Supply For Rxb Controllers

    We recommend the following products: Manufacturer Type Designation Siemens Building Technologies ACX95.320/ALG Power supply 320 mA Siemens Automation and Drives 5WG1 125-1AB01 Power supply 160 mA 5WG1 125-1AB11 Power supply 320 mA 5WG1 125-1AB21 Power supply 640 mA RXB Konnex controller communications RXB Konnex controllers support communication as per the Konnex specification.
  • Page 246: Lte Mode

    The timeswitch zone is a "geographical" zone used for special purposes • Outside temperature zones • Heat distribution zones For further details, refer to the Konnex specification. 10/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 247: Definitions / Tools

    Note A list of all S mode communication objects is located in section 13.5; a detailed description of the Konnex data types in section 0. 11/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 248 All communication objects which operate in LE-mode are described as follows: communication objects Possible partner- Known partner devices function blocks HVACMode 110 HVACS Siemens HVAC-Mode Scheduler Synco RM700 Timeswitch zone 2) 104 PMC Program to HVAC-Mode Conversion Enter the name of the LTE communication object here.
  • Page 249: Supported Tools

    Refer to the EIB manual for more details. Open the project and select a device. To start the parameter setting, select Edit, Edit parameters. 13/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 250: Parameter Setting In Acs

    This information can be found in the ACS description. In the ACS Service program, select Plant, Open to open the plant. To start the parameter setting, select Applications, Parameter settings: 14/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 251: Parameter Setting Using The Handytool

    "Extended" parameter – All parameters. setting Parameter The parameter numbers and the functions are described in the sections below. 15/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Definitions / Tools 28 Feb 2009...
  • Page 252: Operation Of The Handytool Functions

    The parameter numbers are located in sections 13.7 and 13.8 as well as in the sections Note where the functions are described. A table of parameters with enumerations fort he HandyTool is shown in Section 13.9. 16/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 253 P035 Economy cooling setpoint P036 Economy heating setpoint P038 Min supply air temperature P039 Max supply air temperature P240 Device state 17/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Definitions / Tools...
  • Page 254: Extended" Parameter Setting Using Room Unit Qax34.3

    *003 can be set to a value in the range 1 … 255 e.g. 0.2.27 Each address may occur once only in a given plant. 18/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 255: Upload/Download Parameters Using Room Unit Qax34.3

    Press > (Escape) to return to the storage number and select a different number. • If the parameter set matches the connected controller, start download (display flashes). • If connected successfully, "P1" is displayed (see 2.5.2). 19/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 256: Test The Periphery Using Room Unit Qax34.3

    T 42 (0 = Relay deenergized; 1 = energized). T 43 Relay Q34 (0 = Relay deenergized; 1 = energized). 20/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Definitions / Tools...
  • Page 257 To exit test mode, press >- (Escape) 2 - 3 times (depending on the situation). If no further button is pressed for 5 minutes, the controller automatically reassumes Normal mode and all physical outputs are switched back. 21/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 258: Select Communication Mode

    It can be used for operation in – S-mode – LTE-mode and S-mode The Send heartbeat and Receive timeout are described in Section 11.1. 22/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 259: Zone Addressing In Lte Mode (In Conjunction With Synco)

    This zone also includes a Synco device to Zone = ---, 1...31 process the information (e.g. RMH7xx or RMB7xx). 23/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode...
  • Page 260 See also "Master/slave", page 117. Select Communication. ETS3 Professional 24/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode...
  • Page 261 • If in the Geogr. zone or in the Time switch zone one of the values is = –1, the entire zone is "Out of service". 25/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
  • Page 262: Geographical Zone And Time Switch Zone Application Example Rxb With Rmb795

    D: 109 G: 2.2.1 G: 3.7.1 G: 2.1.1 D = device address, G = geographical zone (Apartment.Room.Subzone) Legend 26/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode 28 Feb 2009...
  • Page 263 – Each room group in the RMB795 central control unit All devices which, together, shall form one room group must be assigned the same apartment number. 27/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 264 Each KNX user requires an individual device address – on the floor plan of the preceding page shown as D:11x. The device addresses in our example were assigned in accordance with the bus’ topology. 28/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 265: Implementation Of Application Example

    In agreement with the list created, the settings of the data points with the same names are to be made on the devices during commissioning. commissioning 29/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 266: Heating And Cooling Demand Zone

    Notes zones. • If no 2-pipe fan coil is used, heat and refrigeration demand signals are sent simultaneously to the primary plant. 30/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Select communication mode...
  • Page 267: Applications, Parameters

    Product Finder and insert them in the line. Alternatively: Select View, Open catalog . Select one or several devices, copy and insert them in the line. 31/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 268: Parameter Settings

    Parameter settings The following chapters describe how to set the parameters, which differs only slightly among the two PC tools. Only the display differs. 32/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 269: Room Operating Modes

    Room operating modes Description The room operating modes available with DESIGO RXB are Comfort, Precomfort, Economy and Protection. In addition, there is a frost protection limit, at which, for example, an alarm can be triggered. Each room operating mode has separately adjustable heating and cooling setpoints.
  • Page 270: Overview

    Overview 34/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 271: Determine The Room Operating Mode In Desigo (S-Mode)

    The key factor is the moment at which the state changes (trigger edge). If the mode is later changed by another source of priority 3, the last change applies . 35/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 272: Local Control Of Room Operating Mode Via A Window Contact

    R W C T U 0 1 1 0 0 1.019 0 = Closed 1 = Open DPT_WindowDoor 36/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 273: Central Control Of Room Operating Mode Via Input From The Use Timeschedule

    • Inputs of priority 3 are disabled ( Occupancy time schedule, presence detector, room unit, and Temporary Comfort mode) • Application: Longer periods of non-use of the building 37/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes...
  • Page 274: Central And Local Control Of Room Operating Mode Based On Occupancy

    It controls the room operating mode of a room controller throughout the period when the building is in use. Outside the building-in-use period, it is disabled. 38/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
  • Page 275 R W C T U 0 1 1 0 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 39/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 276 In the case of integration into a building automation and control system, the data is mapped to the following output communication object: PPS2 40/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 277: Central Control Of Room Operating Mode Via The Room Operating Mode Timeschedule

    • The Effective occupancy or Temporary Comfort mode (both Priority 3) can cause the effective room operating mode to change again the last command always applies. 41/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 278: Local Control Of Room Operating Mode Via The Temporary Comfort Mode Input

    R W C T U 0 1 1 0 0 1.017 1 = Trigger DPT_Trigger 0 = Not used 42/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 279: Effective Room Operating Mode

    1 0 1 1 0 20.102 1 = Comfort DPT_HVACMode 2 = Precomfort 3 = Economy 4 = Protection 43/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 280: Desigo Examples

    12.00 to 13.00 (Standby). • In Room 3 the window is opened briefly, once in the morning and once at night (1). 44/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
  • Page 281 (4). However, at the end of the building-in-use period the room operating mode still changes to Economy mode . An alarm can also be tripped, if required. 45/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
  • Page 282 Presence Occupied detector Room 2 Unoccupied Comfort Effective Precomfort room op. mode Room 2 Economy Protection mode 46/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 283: Determine The Room Operating Mode With Third-Party Products (S-Mode)

    The key factor is the moment at which the state changes (trigger edge). If the mode is later changed by another source of priority 3, the last change applies. 47/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 284: Local Control Of Room Operating Mode Via The Window Contact Input

    R W C T U 0 1 1 0 0 1.019 0 = Closed DPT_WindowDoor 1 = Open 48/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 285: Central Control Of Room Operating Mode Via The Room Operating Mode Timeschedule

    Economy are Priority 3 and can therefore later be changed by a presence detector or room unit. • The room operating mode Protection has first priority, and the presence detector and room units are therefore disabled. 49/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 286: Central Control Of Room Operating Mode Via The Use And Occupancy Timeschedules

    (see page 126); alternatively an EIB/KNX presence detector connected to the EIB/KNX bus may be used (see diagram below). The two inputs are OR-linked: If one signals presence, presence applies. 50/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 287 R W C T U 1 0 1 1 0 20.003 0 = Occupied DPT_OccMode 1 = Standby 2 = Unoccupied 51/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 288: Local Control Of Room Operating Mode With A Room Unit

    Auto" means: "Changes to Auto" 1) Comfort mode is operative for the pre-defined Temporary Comfort period (see page 126). The room controller then reverts to Economy. 52/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 289: Local Control Of Room Operating Mode Via The Temporary Comfort Mode Input

    • The Effective occupancy or room unit (both Priority 3) can cause the effective room operating mode to change again the last command always applies. 53/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 290: Effective Room Operating Mode

    R W C T U 1 0 1 1 0 1.001 0 = Off DPT_Switch 1 = On 54/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 291: Third-Party (S-Mode) Examples

    • Overall, the building is in use from 06.00 to 20.00 ( Protection mode from 20.00 to 06.00 hours). • Rooms 1 and 2 must be available from 08.00 to 18.00 hours (Precomfort) 55/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 292 Room without room unit Presence detector Room 2 Occupied Unoccupied Effective room op. mode Comfort Room 2 Precomfort Economy Protection 56/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 293: Determine The Room Operating Mode With Synco (Lte Mode)

    The key factor is the moment at which the state changes (trigger edge). If the mode is later changed by another source of priority 3, the last change applies. 57/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 294: Local Control Of Room Operating Mode Via The Window Contact Input

    In the room controller however, the Priority 3 influences can be enabled forcibly, by ignoring the Enable Comfort input (via the parameter Local Comfort mode ). PPS2 58/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes...
  • Page 295: Central Control Of Room Operating Mode Via Room Operating Mode Input

    The following LTE-mode communication object is provided for central control: K N X Enable Comfort (input) Possible partner-function blocks Known partner devices EnableComfort 110 HVACS Siemens: HVAC-Mode Scheduler Synco RMB795 Timeswitch zone 104 PMC Programme to HVAC-Mode Conversion The states are:...
  • Page 296: Local Control Of Room Operating Mode Via Presence Detector

    (people leave room) Precomfort Economy if room operating mode = Economy Key: Occupied means "changes to Occupied " 60/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 297: Local Control Of Room Operating Mode With A Room Unit

    Auto means: “changes to Auto” 1) Comfort mode is operative for the pre-defined Temporary Comfort period (see page 126). The room controller then reverts to Economy. 61/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 298: Lte-Mode Examples

    • Overall, the building is in use from 06.00 to 20.00 (Protection mode from 20.00 to 06.00 hours). • Rooms 1 and 2 must be available from 08.00 to 18.00 hours (Precomfort) 62/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 299 Occupied Presence detector Room 2 Unoccupied Comfort Effective Room op. mode Precomfort Room 2 Economy Protection 63/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 300: Determine The Room Operating Mode Without A Bus (Stand-Alone)

    If there is no bus connection, the controller assumes the following defaults: • Use = Building in use • Occupancy = Occupied 64/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes...
  • Page 301: Local Control Of Room Operating Mode Via The Window Contact Input

    • The room unit (which is also Priority 3) can cause the effective room operating mode to change again the last command always applies. 65/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 302: Local Control Of Room Operating Mode With A Room Unit

    = Unoccupied Auto Precomfort Comfort Economy Auto Comfort during Temporary Comfort period Protection Auto Protection, unchanged 66/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 303: Stand-Alone Example

    Comfort (2). It reverts to Economy when the window is opened, (3) when the timer period expires (4), or when the /Auto switch is pressed again (5). 67/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 304 Auto on the room unit Room 3 Comfort Effective room operating mode Room 3 Precomfort Economy Protection 68/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room operating modes 28 Feb 2009...
  • Page 305: Setpoint Calculation

    8 present setpoints Frost setpoint (6.1.1) Effective PPS2 room operating mode Effective heating setpoint SpH (6.1.2) Effective cooling setpoint SpC 69/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 306: Bus Output For Current Setpoints

    6.1.3 Bus outputs LTE mode In LTE-mode, the current and effective setpoints are not transmitted to the building automation and control system. 70/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation...
  • Page 307: Set The Setpoints With The Tool

    Select Room temperature setpoints . ETS3 Professional The setpoints can be modified under Room temp setpoints : ACS Service 71/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation...
  • Page 308: Setpoint Adjustment Runtime

    0 1 1 0 0 222.100 3 floating point values - Comfort (°C) DPT_TempRoomSetp - Precomfort (°C) SetF16[3] - Economy (°C) 72/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 309: Central Setpoint Shift

    Setpoints heating (Input) Setpoints cooling (Input) Possible partner Known partner devices function blocks Siemens: TempRoomSetpSetHeat Siemens SBT proprietary Synco RMB795 TempRoomSetpSetCool Geographical zone Setpoints that have been changed by a tool (e.g. HandyTool) are overwritten by Note! STOP PX-KNX during start-up of the room controller! Central setpoint shift •...
  • Page 310: Local Setpoint Shift

    (triplets): Setpoint shift for heating (Input) Setpoint shift for cooling (Input) Possible partner Known partner devices function blocks TempRoomSetpSetHeatShift Siemens: 115 HVACOPT Synco RMB795 TempRoomSetpSetCoolShift HVAC Optimizer Geographical zone Local setpoint shift If setpoints are shifted locally and corrected by the controller, local shift is applied.
  • Page 311 Send heartbeat Value R W C T U 1 0 1 1 0 9.002 Floating point (K) DPT_Value_Tempd 75/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Setpoint calculation 28 Feb 2009...
  • Page 312: Temperature Measurement

    Supply air (cascade) Supply air temperature for cascade control. The sensor is automatically configured as a supply air sensor if application FNC08 is selected. 76/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 313: Averaging Analog Input & Pps2 Interface

    • In order to determine the average value, the sensor must be configured as a room Notes temperature sensor • The signal is not averaged in the case of return air sensors and KNX sensors. 77/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 314: Sensor Correction

    1 0 1 1 0 9.001 Floating point (°C) DPT_Value_Temp Note Invalid temperatures are mapped to the bus as 0 °C. 78/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Temperature measurement...
  • Page 315: Temperature Sensor Input From Konnex Bus

    Room temperature output (Output) Possible partner function Known partner devices blocks TempRoom 390 UHD Siemens: UserHVACDisplay Synco RMH760 / RMB795 Geographical zone RMU710 / 20 / 30 Return air temperature output (Output) Possible partner function Known partner devices...
  • Page 316: Outside Air Temperature Via Konnex Bus (Fnc10, Fnc12, Fnc18)

    Room temperature (Input) Possible partner function blocks Known partner devices TempRoom 321 RTS Siemens: Room Temperature Sensor Synco RMH760 Geographical zone RMU710 / 20 / 30 QAW740 Return air temperature (Input)
  • Page 317: Control Sequences

    The tool displays the actuators suitable for the selected application. Selection occurs at the engineering stage (see page 85). 81/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
  • Page 318: Two-Pipe Fan Coils - With Valve Control

    Selecting the control The control sequence must be selected when the controller is engineered: sequence Heating only, Cooling only or Changeover. 82/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
  • Page 319 The tool displays the actuators suitable for the selected application. The valve type must be selected at the engineering stage (see page 85). 83/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 320: Heating/Cooling Output

    The following communication object is used in LTE-mode: H/C changeover (Input) Possible partner function blocks Known partner devices ChangeOverStatusWater 342 WCOS Siemens: Water Changeover Status Sensor Synco RMU710 / 20 / 30 Distribution zone, heating RMB795 / RMS705 Distribution zone, cooling 8.1.3...
  • Page 321: Actuator Type Selection

    The RXB2… room controllers also support the use of motorized EIB/KNX bus KNX/EIB bus actuators actuators. In the tool, select Bus motorized . 85/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 322 The sequence starts after synchronization. Parameterization The actuator type used must be defined at the engineering stage: Select Edit parameters, Sequences : ETS3 Professional 86/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
  • Page 323 This is especially important for fast running actuators. For electromechanic actuators, the actuator running time can be adapted. For fast actuators , select valve type "Motoric 3rd party devices ". 87/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 324 0 ... 360 s *062 Offset heating valve 0 ... 360 s *071 Offset cooling valve 0 ... 360 s *072 88/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 325: Values Representing Valve Actuator Positions

    Since EIB/KNX bus actuators are available from a variety of manufacturers, the name of their S-mode input communication object varies accordingly. 89/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 326 The two fields at the bottom of the dialog box only appear if "LTE and S-mode" was selected under Communication . Select Sequences . ACS Service 90/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 327: Valve Exercising Feature

    Heating and cooling alternately, with the Heating value Motorized actuators: Heating and cooling valve driven to the Heating position 91/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 328: Fan Coils With Damper Control

    Select Sequences . ETS3 Professional 92/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
  • Page 329: Value Representing Damper Actuator Positions

    R W C T U 1 0 1 1 0 5.001 0...100% 0 = 0% DPT_Scaling 255 = 100% 93/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 330: Overriding The Damper Actuator

    Valid Valid The full travel of the damper is 0…100%. The actuator moves to the position defined by the heating value. 94/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
  • Page 331: Fan Coils With An Electric Heating Coil

    Cooling valve Electric reheater Safety thermostat Return air sensor 1-step Modulating YR, Y 100% 100% TR [°C] TR [°C] 95/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 332: 2-Pipe Fan-Coils With Electric Reheater

    Changeover with Change-over disabled electric heater (see page 97) TR [°C] Further details: see sections 8.1.3 through 8.1.7. 96/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 333: The Electric Reheater

    R W K T U 0 1 1 0 0 1.003 0 = Disabled DPT_Enable 1 = Enabled 97/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 334 See Parameters in the last column of the table below Short name Basic setting Parameter Electric heater Modulating *056 1-step Modulating 98/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 335 Select Sequences, Power consumption : ACS Service HandyTool Parameter Short name Basic setting *057 Power consumption el heater 99/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 336: Fan-Coils With Lthw Radiator (Fnc18)

    The radiator as an additional heating sequence has its own settings for the valve actuator and runtime. The principles are described in section 8.1.4 . 100/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 337 Running time heat surface valve 150s 0…360 s *064 (motorized actuators) Offset heating surface valve 0 ... 360 s *066 101/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 338: Position Values For Tediator Valve Actuators

    2 bus signals (see 11.5 , Heating and cooling demand ). In S-mode, this demand is summarized in Heating demand room . 8.5.4 Radiator valve actuator override See also section 8.1.7. 102/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences...
  • Page 339: Downdraft Compensation

    The heat output calculated by the controller is achieved as follows: LTHW radiators with The valve is opened to the heat output value [%]. motorized valve actuators 103/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 340 1600 seconds "OPEN" (1s On, 1 s Off) 400 s "CLOSE" (1s On, 19 s Off) The long cycle time ensures that the valves are fully opened and closed. In a network containing several room controllers, the opening of the Siemens thermic actuators is staggered to prevent the heating load from fluctuating.
  • Page 341: Outside Air Damper Fan Coils ("Economizer", Fnc10, Fnc12)

    SpEcm Economizer setpoint = Outdoor temp. min. damper position SpFr Frost protection limit value TO [°C] SpFr SpEmc SpC 105/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 342: Configuration And Parameterization

    1K between the Outside air temp. min. damper pos. setpoint and the cooling setpoint of the effective room operating mode. 106/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12...
  • Page 343: Enabling Of The Function

    1 = Enable = automatic control The following communication object is used in LTE-mode: Enable dampers (Input) Possible partner function blocks Known partner devices 115 HVACOpt Siemens: DisableDamper HVAC-Optimizer Geographical zone The use of the outside-air damper can only be implemented in conjunction with the RXB21.1 controller.
  • Page 344: Overriding The Outside Air Damper

    Room controller FNC08 This function is possible in conjunction with motorized valve actuators only . Note! STOP 108/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 345: Parameterizing

    0.5 °C *038 temperature Maximum supply air 35 °C Comfort cooling setpoint to 40 °C 0.5 °C *039 temperature 109/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Control sequences 28 Feb 2009...
  • Page 346: Supply Air Inputs / Outputs

    Supply air temperature output (Output) Possible partner function Known partner devices blocks TempSupplyAir 390 UHD Siemens: UserHVACDisplay Synco RMH760 / RMB795 Geographical zone RMU710 / 20 / 30 When "supply air " is configured, the controller retrieves this value after a reset.
  • Page 347: Fan Control

    Heating sequence Cooling sequence 1. Fan speed 3 2. Fan speed 3 3. Fan speed 3 TR [°C] 111/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control 28 Feb 2009...
  • Page 348 Receive timeout Value R W K T U 0 1 1 0 0 5.001 0...100% DPT_Scaling 255 = 100% 112/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control 28 Feb 2009...
  • Page 349: Fan Parameter Setting

    User Fan Speed Setting Geographical zone Fan parameter setting Select Fan control, Fan speeds. ETS3 Professional 9.2.1 9.2.2 7.1.2 9.2.4 9.2.3 113/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control 28 Feb 2009...
  • Page 350: Fan Speeds And Control

    Single-speed fan control with relay Q14. 2-speed Two-speed fan control with relays Q14 and Q24. Three-speed fan control with relays Q14, Q24 and Q34. 3-speed 114/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Fan control...
  • Page 351: Minimum On Time

    Economy ) is available even if no return air sensor is parameterized. Note! For tool architecture reasons, those time values are visible and settable in ACS and in the HandyTool although not supported by the controller. 115/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 352 Precomfort and Comfort , fan speed 1 is enabled for the minimum runtime and the periodic fan kick starts. • A QAX34.1 room unit displays the value of B1. 116/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 353: Master/Slave

    The slave controller is controlled by a master controller via the KNX bus. The master and slave controllers operate in parallel. The room temperature is measured only by the master. 117/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 354: S-Mode

    (Company Specific) Note You need four group addresses (GA1 … GA4) independent of the number of slaves. Select Master/Slave: ETS3 Professional 118/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Master/slave 28 Feb 2009...
  • Page 355: Window Switch (S-Mode)

    This binding ensures that both controllers react when a presence detector becomes active. If several slaves are equipped with presence detectors, the correct evaluation is required for the logic block. 119/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 356: Lte Mode With Zones

    Geogr. zone und M/S zones need not be the same. However, every day work is easier because you see directly to which master a slave belongs. Select Master/Slave: ACS Service 120/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 357: Window Switch (Lte Mode)

    For master/slave mode, only the master's presence detector is evaluated without special measures, which also influences the slave controllers. Presence detectors on the slaves are NOT considered. 121/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 358: Peripheral Functions

    Master Slave RXB... RXB... room units with push- buttons for setpoint adjustment. Auto QAX33.1 QAX34.1 122/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Master/slave 28 Feb 2009...
  • Page 359: General And Central Functions

    Central functions . See Section 11.1 11.2 11.3 11.4 11.5 11.8 11.10, 11.14 11.16 123/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
  • Page 360 We recommend to use this feature. HandyTool The general and central functions are set with parameters 117 – 137. For detailed information, refer to the individual sections. 124/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 361: Send Heartbeat And Receive Timeouts

    HandyTool Parameter Short name Basic setting *128 Receive timeout 60 min Send heartbeat *127 45 min 125/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
  • Page 362: Digital Inputs

    0 ... 90 min 1 min *119 Off-delay occupancy detector 5 min 0 ... 90 min 1 min *120 126/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
  • Page 363: Heating And Cooling Demand

    In LTE mode the energy demand is determined by two signals: Heating coil energy demand (Output) Possible partner function blocks Known partner devices EnergyDemAH 154 AHDTTU Siemens: Air Heater Energy Demand Synco RMH760 Distr. zone, heating Transformer TU RMU710 / 20 / 30...
  • Page 364: Heating/Cooling Signal Output

    FNC18 generates an additional energy demand signal for the heating surface: Energy demand heating surface (Output) Possible partner function blocks Known partner devices EnergyDemRD 153 RHDTTU Siemens: Radiator Energy Demand Synco RMH760 Distr zone, heating Transformer TU RMU710 / 20 / 30...
  • Page 365: Boost Heating (Morning Warmup, 2)

    This function is used to raise the temperature in a room as quickly as possible to the Precomfort heating setpoint at the end of the night setback period. Objective: Preheat the room for heating. 129/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 366: Night Purge (Night Purge, 4), (Fnc10, Fnc12)

    Terminating the function – The function is disabled via the building automation and control system. – When the outside air damper is disabled 130/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 367: Precooling (Precool, 5)

    – Thermal valves are preheated (see page 86). – The control algorithm but not the complete application is restarted. Limitations Test mode is possible only with S-mode objects! 131/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 368: Emergency Heating (Emergency Heat, 8)

    Temperature control is switched off and the heating and cooling coils are disabled. Outside air is only introduced if the room temperature is between the Economy heating and Economy cooling setpoints. 132/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 369: Free Cooling (Freecool, 10)

    The function must be enabled via the building automation and control system (communication object Application mode , see page 128). Terminating the function The function is disabled via the building automation and control system. 133/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 370: 11.15 Alarm

    0 1 1 0 0 1.003 Ja (fix 42 hours) 0 = Disabled DPT_Enable 1 = Enabled 134/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
  • Page 371: 11.15.2 Lte Mode

    Here, the device listens on the bus and sends an alarm when it has highest alarm priority. This ensures that the management station does not miss any alarms. AlarmInfo_CS (Output) Possible partner function blocks Known partner devices Siemens AlarmInfo_CS Synco RMU710 / 20 / 30, RMH760, RMB795, RMS705 Broadcast...
  • Page 372: 11.17 Free Inputs/Outputs

    May be used freely in applications with single-speed or 2-speed fan, (see page 114). The setting of parameters for unused inputs is described in Section 11.2, page 126. 136/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 373: 11.17.1 Digital Inputs On The Knx Bus

    1.001 0 = Off (voltage-free) 0 1 1 0 0 DPT_Switch 1 = On (AC 24V) 137/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions 28 Feb 2009...
  • Page 374: 11.17.3 Mapping The Sensor B1 To The Konnex Bus

    Device state *240 Hinweis In Service mode the device state is always = 0 because the application is not running. 138/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies General and central functions...
  • Page 375: Room Unit

    Standard display (only room units with LCD) Room temperature *109 Standard display (only room units with LCD) Relative *110 139/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room unit 28 Feb 2009...
  • Page 376 LCD display. Parameter Value HandyTool Temperature unit (only room units with LCD) *108 Celsius (°C) (basic setting) Fahrenheit (°F) 140/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room unit 28 Feb 2009...
  • Page 377 If "Absolute setpoint adjustment" is selected, the LCD panel displays a scale which illustrates the adjustment as it happens: 10385Z20 Note To reset the setpoint shift, refer to page 141/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Room unit...
  • Page 378: Knx Information

    • No application selected (see 4.1). flashing • Loading. – Download from ETS3 or ACS. – Room unit QAX34.3 in HandyTool mode. 142/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information...
  • Page 379: Startup Delay

    • Each group address must have a receiver to acknowledge the telegram, otherwise unwanted repeat-telegrams are generated. • For additional hints for reducing the bus load see pages 25 and 90. 143/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 380: S-Mode Communication Objects For Fnc

    Triac Y4 0 1 1 0 0 1.001 DPT_Switch Window switch input 0 1 1 0 0 1.019 DPT_Window_Door 144/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 381: 13.5.2 S-Mode Output Communication Objects

    Supply air temperature output 0 1 1 0 9.001 DPT_Value_Temp 0 1 1 0 1.019 DPT_Window_Door 37, 49 Window switch output 145/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 382: Ltemode Communication Objects

    Room Temperature Sensor – RNATS Return Air Temperature Sensor – FSA Fan Speed Actuator – ALSrc 1002 Alarm Source 146/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 383: Handytool Parameters By Number

    Outside temp min damper pos Running time outside air damper Minimum damper position Outside temp 0% valve pos Outside temp max valve pos 147/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information...
  • Page 384 Operating system version KNX interface version Device state HandyTool: In FNC20, runtime damper heating HandyTool: In FNC20, runtime damper cooling 148/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 385: Handytool Parameters Sorted Alphabetically

    Heating coil outp bus valve Heating surface output bus valve actuator KNX interface version Local Comfort mode 139, Master/slave 149/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 386 Running time outside air damper Send heartbeat 139, Setpoint display 139, Setpoint offset range 139, Standard display Temperature sensor. 150/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 387 HandyTool: In FNC20, output bus damper actuator HandyTool: Cannot be mapped HandyTool: Visible, but not used by application FNC08: always Supply air 151/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information...
  • Page 388: Handytool Enumerations

    Rapid ventilation (earlier: air purge) Reset setpoint offset Night purge Application set Application version Operating system version KNX interface version Device state 152/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 389: 13.10 Data Point Type Description

    9 = Fan only 10 = Free Cool 11 = Ice 20 = noDem 255 = NUL Other: Reserved 153/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 390 DPT_TempRoom 3 floating point values (16) (16) (16) SetpSetShiftF16[3] - Comfort (3 x EIS5) - Precomfort - Economy 154/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies KNX information 28 Feb 2009...
  • Page 391: Faqs

    Check to make sure that neither the operating booklet nor the plant image is active. Both applications cause a lot of bus traffic and thus slow down reading back parameters. 155/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 392 Answer for LTE mode: Master/slave zones must be identical for master and slave. Create master/slave group addresses and add communication object. Answer for S-mode: 156/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 393 Example: an RXB controller receives the room temperature from a bus sensor. A bus display is used to display the room temperature. The display must get the signal directly from the bus sensor. 157/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05...
  • Page 394: Integrate Rxb In Desigo/Synco

    Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 158/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 395: Case 2: Integration Into Desigo

    DESIGO • Energy demand: to DESIGO DESIGO INSIGHT PXC... PXC... PX KNX PXM20 Individual addressing Konnex 159/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 396: Case 3: Display In Desigo, With Shared Synco Time Scheduler

    Konnex Geographical zone Synco Synco Synco Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 160/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 397: Case 4: Display In Desigo/Synco, With Shared Synco Time Scheduler

    Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 161/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 398: Case 5: Display In Desigo, And Separate Time Schedulers

    Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 162/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 399: Case 6: Separate Display, And Separate Time Schedulers

    Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 163/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 400: Case 7: Separate Display, And Shared Synco Time Scheduler

    Geographical zone Synco Synco Synco Geographical zone Geographical zone Timeswitch zone Heating demand zone Cooling demand zone 164/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies Integrate RXB in DESIGO/Synco 28 Feb 2009...
  • Page 401 If a controller has been commissioned with ETS in S-Mode and is now being used with ACS in LTE-Mode : You must delete the group addresses separately with ETS; otherwise communication problems may occur. 165/166 Siemens RXB (KNX) application library FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05 Building Technologies...
  • Page 402 166/166 Building Technologies RXB application library from V2.36 FNC Description of functions for FC-10, FC-11, FC-12CM110385en_05 – 1BTabl Building Automation 1BTable of contents – Fehler! Formatvorlage nicht definiert. 28 Feb 2009...
  • Page 403 RXB application library (KNX) FNC – Fancoil applications from FC-10, FC-11, FC-12 (See separate document CM110385 for the FNC description of functions). For RXB... Application Page 21.1 21.1 22.1 Two-pipe fan coil with changeover FNC02 FNC03 Two-pipe fan coil with changeover and electric reheater FNC04 Four-pipe fan coil FNC05...
  • Page 404 2/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies 30.11.2007...
  • Page 405 Heating sequence. Cooling sequence. Heating/cooling valve. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 3/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover 30.11.2007...
  • Page 406 /Auto and fan speed control, and LCD display. Compatible controllers. FNC02 is supplied with RXB21.1/FC-10. 4/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover...
  • Page 407 Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 5/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 –...
  • Page 408 Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 6/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover 30.11.2007...
  • Page 409 Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
  • Page 410 8/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC02 – Two-pipe fan coil with changeover 30.11.2007...
  • Page 411 Contactor or solid state relay for electric heating TR [°C] TR [°C] coil. 9/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater 30.11.2007...
  • Page 412 /Auto and fan speed control, and LCD display. Compatible controllers. FNC03 is supplied with RXB22.1/FC-12. 10/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater...
  • Page 413 7) External fuse, max. 10 A (protects pcb tracks). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 11/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 –...
  • Page 414 5 min On-delay occupancy detector 0 ... 90 min 5 min Off-delay presence detector 12/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater...
  • Page 415 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB22.1 with application group FC-12 RXB22.1/FC-12 Example Note The controllers are delivered with the basic settings shown above.
  • Page 416 14/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC03 – Two-pipe fan coil with changeover and electric reheater 30.11.2007...
  • Page 417 Heating sequence. Cooling sequence. Heating valve. Cooling valve. Fan speed 1. TR [°C] Fan speed 2. Fan speed 3. 15/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil 30.11.2007...
  • Page 418 Available with temperature sensor, setpoint adjuster, button for /Auto and fan speed control, and LCD display. Compatible controllers. FNC04 is supplied with RXB21.1/FC-10. 16/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil...
  • Page 419 Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 17/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 –...
  • Page 420 Precooling, free cooling Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 18/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil 30.11.2007...
  • Page 421 Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
  • Page 422 20/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC04 – Four-pipe fan coil 30.11.2007...
  • Page 423 Safety thermostat electric reheater. Fan (1… 3-speed). Heating valve. Cooling valve. K N X Electric reheater. 21/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater 30.11.2007...
  • Page 424 Effective cooling setpoint. Heating sequence. Cooling sequence. Fan speed 1. Fan speed 2. Fan speed 3. 22/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater 30.11.2007...
  • Page 425 /Auto and fan speed control, and LCD display. Compatible controllers. FNC05 is supplied with RXB22.1/FC-12. 23/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater...
  • Page 426 7) External fuse, max. 10 A (protects pcb tracks). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 24/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 –...
  • Page 427 Enabled / Disabled Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 25/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC05 – Four-pipe fan coil with electric reheater 30.11.2007...
  • Page 428 Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB22.1 with application group FC-12 RXB22.1/FC-12 Example Note The controllers are delivered with the basic settings shown above.
  • Page 429 Cooling valve. Fan speed 1. Fan speed 2. TR [°C] Fan speed 3. 27/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 – Four-pipe fan coil with room supply air cascade 30.11.2007...
  • Page 430 /Auto and fan speed control, and LCD display. Compatible controllers. FNC08 is supplied with RXB21.1/FC-10. 28/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 – Four-pipe fan coil with room supply air cascade...
  • Page 431 4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 29/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC08 –...
  • Page 432 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
  • Page 433 Outside air damper. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 31/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC10 – Two-pipe fan coil with changeover and outside air damper...
  • Page 434 /Auto and fan speed control, and LCD display. Compatible controllers. FNC10 is supplied with RXB21.1/FC-11. 32/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies – Two-pipe fan coil with changeover and outside air damper...
  • Page 435 4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 33/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies –...
  • Page 436 0 ... 90 min 5 min 0 ... 90 min 5 min Off-delay presence detector 34/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies – Two-pipe fan coil with changeover and outside air damper...
  • Page 437 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 Example Note The controllers are delivered with the basic settings shown above.
  • Page 438 36/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies – Two-pipe fan coil with changeover and outside air damper 30.11.2007...
  • Page 439 Outside air damper. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 37/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper 30.11.2007...
  • Page 440 /Auto and fan speed control, and LCD display. Compatible controllers. FNC12 is supplied with RXB21.1/FC-11. 38/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper...
  • Page 441 4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 39/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 –...
  • Page 442 Enabled Reset setpoint offset Enabled / Disabled Disabled Master/slave Master/slave Master or slave Master 40/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper 30.11.2007...
  • Page 443 Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 Example Note The controllers are delivered with the basic settings shown above.
  • Page 444 42/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC12 – Four-pipe fan coil with outside air damper 30.11.2007...
  • Page 445 Q14 Fan speed 1. Q24 Fan speed 2. TR [°C] Q34 Fan speed 3. 43/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 – Two-pipe fan coil (changeover) and radiator 30.11.2007...
  • Page 446 /Auto and fan speed control, and LCD display. Compatible controllers. FNC18 is supplied with RXB21.1/FC-11. 44/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 – Two-pipe fan coil (changeover) and radiator...
  • Page 447 3) Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). 4) Do not connect the fans in parallel (or use cut-off relays). 45/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12...
  • Page 448 4) Do not connect the fans in parallel (or use cut-off relays). Note A current list of compatible devices is available in the DESIGO RX hardware overview (N3804). 46/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 –...
  • Page 449 No display / Room Room temperature. temperature / Setpoint Setpoint display Absolute / Relative Relative 47/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC18 – Two-pipe fan coil (changeover) and radiator 30.11.2007...
  • Page 450 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11 Example Note The controllers are delivered with the basic settings shown above.
  • Page 451 Cooling sequence. Damper actuator. Fan speed 1. Fan speed 2. Fan speed 3. TR [°C] 49/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC20 – Four-pipe fan coil, controlled by one damper 30.11.2007...
  • Page 452 Do not exceed the max. simultaneous load on outputs Y1 ... Y4: 9.5 VA (see data sheet 3873). Do not connect the fans in parallel (or use cut-off relays). 50/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12...
  • Page 453 No display / Room Room temperature. temperature / Setpoint Setpoint display Absolute / Relative Relative 51/52 Siemens RXB application library (KNX) FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_03 Building Technologies FNC20 – Four-pipe fan coil, controlled by one damper 30.11.2007...
  • Page 454 Master or slave Master Ordering The room controllers can be ordered preloaded with the application described here. When ordering, specify the quantity, DESIGO RXB device name, type code and application group. Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10 Example Note The controllers are delivered with the basic settings shown above.
  • Page 455 KN X DESIGO™ RXB, RXL Installation guide CM110381en_01 Building Technologies 28 Feb 2009...
  • Page 456 Bus lengths and distances ..............17 4.5.4 Network address ..................19 4.5.5 Limits .......................19 4.5.6 Zones and zone addresses..............19 4.5.7 Area and line couple, IP router..............20 4.5.8 Filter worksheets ..................21 2 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Contents 28 Feb 2009...
  • Page 457: About This Document

    The table below lists the third-party trademarks used in this document and their legal owners. The use of trademarks is subject to international and domestic provisions of the law. Trademarks Legal owner DESIGO Siemens Building Technologies Synco Siemens Building Technologies Konnex®, KNX®, EIB® Konnex Association, B - 1831 Brussels-Diegem Belgium, http://www.knx.org/...
  • Page 458: Copyright

    1.3.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.3 Quality assurance These documents were prepared with great care.
  • Page 459: Introduction

    The RXB controllers are compatible with the DESIGO and Synco systems from RXB controller Siemens Building Technologies. The communications component on the RXB controllers are based on Konnex technology and support the S-mode and LTE mode. The devices are certified for Konnex and are labeled with the KNX logo.
  • Page 460: Periphery Wiring (Without Bus)

    3.1.2 Transformer design AC 24 V The DESIGO RXB controller is powered by AC 230 V; the RXL controller by AC 24 Controllers with AC 230 V power internally generates the AC 24 V power supply for connected field devices.
  • Page 461: Signal Wiring

    – The KNX bus wire must be connected with the proper polarity. – The simple wiring length between controllers, or controller and room device must be considered for the overall wiring length of the KNX bus. 7 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies...
  • Page 462: Relay Outputs

    • The maximum power is 1.8 kW ohm load. Larger loads close the contact too much. • A external fuse of max. 10 A is planned to protect room controller circuits. 8 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies...
  • Page 463: Connect Room Units In Master/Slave Configurations

    Master Slave RXB... / RXL... RXB... / RXL... units with buttons for setpoint shift. Auto QAX33.1 QAX34.1 9 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Periphery wiring (without bus) 28 Feb 2009...
  • Page 464: Installation Notes

    EMC). Cable screens must always be throughout and have solid coverage. Any break in the screening significantly reduces the effect of screening. 10 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Periphery wiring (without bus)
  • Page 465 The bus wire (KNX, PPS2) cannot be wired in parallel to increase the cross section. Parallel wiring is, however, permitted for power, valve actuators and analog signals, e.g. temperature sensors. 11 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies...
  • Page 466: Konnex Bus Technology

    (Larger value requires a proportional shortening of permissible cable lengths). Cable screen not required (devices without screened connection) Bus terminating resistor Not required 12 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
  • Page 467: Bus Cable Screening

    (3 x AC 400 V). 4.2.2 Terminating resistor Konnex networks do NOT require bus terminating resistors. 13 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
  • Page 468: Bus Power Supply

    Each controller consumes 5 mA. Thus, select the supply according to the number of controllers. We recommend the following products: Manufacturer Product No. Designation Siemens Building Technologies ACX95.320/ALG Power Supply 320 mA Siemens Automation Technologies 5WG1 125-1AB01 Power Supply 160 mA...
  • Page 469: Device Interface Specification (Rxb/Rxl)

    = Heart Beat RXL communication is proprietary and NOT Konnex compatible. It serves to RXL communication communicate with a DESIGO management station of a Synco control unit. 15 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology...
  • Page 470: Engineering Notes

    3.15.0 Area 2 2.0.0 Main line 2 2.1.0 2.2.0 2.3.0 2.15.0 Area 1 1.0.0 Main line 1 0.1.0 0.2.0 1.1.0 1.2.0 1.3.0 1.15.0 16 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
  • Page 471: Bus Topologies

    Bus power supply max. 350 m. Distance between two bus devices max. 700 m. Total length of all lines on one line max. 1,000 m. 17 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology 28 Feb 2009...
  • Page 472 Total length The permissible total length of 1,000 meter in the line is exceeded, if device N5 is integrated in the bus at the given bus wiring. 18 / 22 Siemens Installation guide RXB, RXL CM110381en_01 Building Technologies Konnex bus technology...
  • Page 473: Network Address

    Zones and zone addresses In LTE mode (together with Synco devices), set up various zones. We recommend using worksheets for engineering. See Synco intranet, Excel worksheet under Synco700: https://intranet10.sbt.siemens.com/business/building_comfort/products/controllers_ hvac/ Relevant zone and their settings ranges for RXB / RXL Geographic zones: •...
  • Page 474: Area And Line Couple, Ip Router

    Note For large plants with Synco, use Siemens area/line couplers as of version R2 (stamped R2), since only these couplers contain the LTE filter worksheet (see Section 4.5.8.2). routers are required when you need to connect a KNX network to an IP Use of IP routers network.
  • Page 475: Filter Worksheets

    Additional information is available in the product and function description (including with each device) or at: www.automation.siemens.com/et/gamma/ Note For large plants with Synco, use Siemens IP routers as of version R4 (stamped R4), since only these IP routers contain the LTE filter worksheet (see Section 4.5.8.2). 4.5.8 Filter worksheets 4.5.8.1...
  • Page 476 Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Phone +41 41-724 24 24 Fax +41 41-724 35 22 © 2009 Siemens Switzerland Ltd www.buildingtechnologies.siemens.com Subject to change 22 / 22 Siemens Installation guide RXB, RXL CM110381en_01...