Working with different tools
It is possible to prepare the RXB controllers in the office by setting the parameters in
advance, so that only the physical address has to be entered on site. The HandyTool
contains a "limited" parameter-setting option which can be used for this purpose.
The preparatory work would then probably be carried out with ACS or ETS rather than
with the HandyTool.
Special caution is required (in relation to data consistency) when using more than one
tool.
Step 1
HandyTool
ACS
ETS
*
An upload is necessary to avoid losing the data from Step 1
**
No ETS project (therefore no upload possible)
***
The ETS project is NOT updated
If a controller has been commissioned with ETS in S-Mode and is now being used
with ACS in LTE-Mode :
You must delete the group addresses separately with ETS; otherwise
communication problems may occur.
RXB (KNX) application library
Working with different tools
HandyTool
ACS Service
X ***
FNC Description of functions for FC-10, FC-11, FC-12
Step 2
ETS
( ) *
X **
X **
X ***