Temperature Sensor Outputs On The Konnex Bus - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Note
76/140
Siemens
Building Technologies
7.1.5

Temperature sensor outputs on the Konnex bus

To map the local temperature measurement in a building automation and control
system, the following two output communication objects are used:
RXB... Room controller
+
O
R
The value of the communication object Room temperature output is not filtered (not
smoothed).
Sending takes place only if room "Room" is parameterized for the temperature sensor
B1.
The value transmitted as the Effective room Temperature is the filtered (smoothed)
value of the communication object Room temperature output or Return air temperature
output, or the average (see 7.1.3):
Room temperature output (output communication object)
Effective room temperature (output communication object)
Flags
Type
R W C T U
1 0 1 1 0 9.001
DPT_Value_Temp
Invalid temperatures are mapped to the bus as 0 °C.
In LTE mode, the room air temperature from directly connected sensors is mapped as
follows:
Room temperature output (output)
TempRoom
Geographical zone
RXB (KNX) Applications library
Temperature measurement
Room temperature output
Effective room temperature
Send heartbeat
Yes
Possible partner function
blocks)
390 UHD
UserHVACDisplay
CLC and RAD description of functions for CC-02 CM110384en_03
10384Z15en
Value
Floating point (°C)
Known partner devices
Siemens:
Synco
RMH760 / RMB795
RMU710 / 20 / 30
28 Feb 2009