Upload/Download Parameters Using Room Unit Qax34.3 - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Caution
STOP
Upload
Download
Siemens
Building Technologies
2.6
Upload/download parameters using room
unit QAX34.3
This function requires a QAX34.3 with index D or higher!
The HandyTool can save 5 different controller parameter sets.
These are uploaded from a fully parameterized controller using the Upload function.
Download allows for transferring such a data set to one or several controllers
(prerequisite: same controller type).
The address, and for LTE the zones, must be adjusted (see 2.5.2).
Download allows for changing also critical values.
As a worst case scenario, components (controllers/actuators or other plant
parts) may be destroyed.
Start parameterization mode:
• Press buttons < , > and – simultaneously for about 2 s until the display turns dark.
• Release the buttons.
• Press button – twice briefly.
• Press buttons + and – simultaneously for approx. 2s
• Press button + twice briefly.
The display now shows
Use + and / or – to choose between the following modes:
0 =
Normal mode (normal room unit functions).
1 =
Test mode (see 2.7).
2 =
Display mode (see 2.5.2).
3 =
Parameterization mode (see 2.5.2).
4 =
Upload.
5 =
Download.
6 =
Service mode.
If
4 or
5 is displayed, this mode can be selected via < (Enter).
The storage number (c1) is displayed and can be changed via + / – . Select the desired
storage (1 .. 5) via < (Enter).
• If storage is empty, upload begins and the display flashes.
OK is displayed after successful upload.
• If the storage is full, "dEL" for "Delete?" is displayed.
Pressing <(Enter) at this time overwrites the existing set.
If you press > (Escape), the storage number which you can change via + / – is
displayed.
• If the parameter set does not match the connected controller, error message "Err" is
displayed.
Press > (Escape) to return to the storage number and select a different number.
• If the parameter set matches the connected controller, start download (display
flashes).
• If connected successfully, "P1" is displayed (see 2.5.2).
RXB (KNX) Applications library
Definitions / Tools
0 (mode 0).
CLC and RAD description of functions for CC-02 CM110384en_03
The display goes dark.
17/140
28 Feb 2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents