Four-pipe fan coil, controlled by one damper
Plant diagram
N1
Room controller.
R1
Room unit with temp.
sensor.
B1
Return air sensor.
D1
Window switch.
D2
Presence detector.
Q1
Fan (1... 3-speed).
YM
3-position damper actuator.
Operating diagrams
Y
Output signal.
TR
Room temperature.
SpH
Effective heating setpoint.
SpC
Effective cooling setpoint.
H
Heating sequence.
C
Cooling sequence.
YM
Damper actuator.
Q14
Fan speed 1.
Q24
Fan speed 2.
Q34
Fan speed 3.
Siemens
Building Technologies
•
Heating with LTHW and cooling with CHW.
•
3-position damper actuator.
•
Automatic or manual fan control.
YM
N1
K N X
R
Y [%]
H
N
100
0
SpH SpC
Y
H
Q34
Q24
Q14
SpH
SpC
RXB application library (KNX)
FNC20 – Four-pipe fan coil, controlled by one damper
Q1
T
B1
T
R1
D1
C
YM
TR [°C]
C
TR [°C]
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
FNC20
K NX
D2
CM110672en_03
30.11.2007
R
49/52