Summary of Contents for Siemens Synco living QAX913
Page 1
Synco™ living Mounting and commissioning Edition 1.0 QAX9x3 Series A CE1C2740en Building Technologies 13.12.2010...
Page 3
Congratulations … … on choosing the Siemens Synco™ living system and thank you for pur- chasing the central apartment unit! The present document describes how to mount and commission the central apartment unit and the other system components. First, please familiarize yourself with the operating philosophy of the central apartment unit.
Configure doors (QAX913 only) ............31 Configure meter.................. 31 Synergyr..................31 Allocation ..................32 Source..................32 Configure heat/cooling energy meter........... 32 Configure hot water meter ............33 4 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents 13.12.2010...
Page 5
Assign rooms to room groups............50 Cooling release output..............50 Configure ventilation ................51 Step selector................51 Humidity sensor ................51 Indoor air quality sensor .............. 52 5 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents 13.12.2010...
Page 6
Connect WRI982 consumption data interface ......73 Connect door contacts (QAX913 only)..........74 Connect temperature sensor (QAX913 only) ........74 Connect fault inputs 1 – 8 (QAX913 only) .......... 74 6 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents...
Page 7
Remote setting clock slave ..............91 Calendar zone (holidays and special days) ........92 DHW zone..................92 Set distribution zone................93 Exit the "Commissioning" menu ............... 94 7 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents 13.12.2010...
Page 8
Minimum operating time night cooling..........109 Reference room night cooling ............109 Outside temperature limit value night cooling ........110 Room outside temperature delta night cooling......... 110 8 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents 13.12.2010...
Page 9
Device list repeater ................122 Data backup ................... 122 System limits....................123 System limitations (TP1 bus) ............. 123 Limitations per central apartment unit........123 Limitations per room ..............123 9 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents 13.12.2010...
Page 10
Communication ................... 124 Protocol..................124 Maintenance/service ................... 124 Peripheral devices .................. 124 Restore factory settings..............124 Manual control of the radiator control actuator......... 124 Disposal ....................... 125 Index......................126 10 / 134 Siemens Synco™ living CE1C2740en Building Technologies Table of contents 13.12.2010...
• Application-related technical data are only guaranteed in connection with the Siemens Synco™ living system. When using together with third-party products not specified by Siemens, user must ensure functionality. In that case, Siemens does not provide any services or warranty. 11 / 134 Siemens Synco™...
• The typical range between transmitter and receiver in residential buildings is 30 m, or across 2 floors, or 2 concrete ceilings. But depending on the type 12 / 134 Siemens Synco™ living CE1C2740en Building Technologies Mounting and installation...
If greater distances are to be covered, RF repeaters should be used. Central apartment unit QAX913 dimensions Dimensions in mm Dimensions of the base Dimensions in mm 13 / 134 Siemens Synco™ living CE1C2740en Building Technologies Mounting and installation 13.12.2010...
Insert a screwdriver (size 3) in the first and then in the second slot at the bottom of the unit, slightly push it and then turn to unlock. 14 / 134 Siemens Synco™ living CE1C2740en Building Technologies Mounting and installation 13.12.2010...
45° in the base (left and right). Then, swing it downward until it en- gages. The central apartment unit is now ready for commissioning. 15 / 134 Siemens Synco™ living CE1C2740en Building Technologies Mounting and installation 13.12.2010...
Run the cables under the straps provided and – after connection – ensure strain relief with the help of cable ties. 16 / 134 Siemens Synco™ living CE1C2740en Building Technologies Mounting and installation 13.12.2010...
Page 17
Operating voltage, live conductor AC 230 V Protection by extra-low voltage CE-, CE+ Connection data bus KNX TP1- and KNX TP1+ Ground for universal input Universal input Strap for cable ties 17 / 134 Siemens Synco™ living CE1C2740en Building Technologies Mounting and installation 13.12.2010...
You must first enter the basic configuration at the central apartment unit to connect devices. Switch on the central apartment unit The central apartment unit must be switched on to enter the basic configura- tion. 18 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Menu/ok button. If no button is pressed on the expert level for a certain period of time, the central apartment unit automatically returns to the user level. 19 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
For rooms with an air conditioner used for heating. Usually, the standard heating types are enough. Customize settings only in plants with greatly differing control behavior (see page 99). 20 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Page 21
> Rooms > Room X > Room X: Predefined room names are provided for quick and easy entry of room names. You can adjust a predefined room name. 21 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
> Room groups > Room group X > Room group X: Function Define the function needed for the room group. Main menu > Commissioning > Basic configuration > Room groups > Room group X > Function: 22 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Room group 2 --- (Inactive) Room group pumps The room group pump is commissioned when the relevant output terminal closes. Room group pumps and DHW diverting valve: 23 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
The return temperature of both room groups can be limited: Minimum or maximum limitation. A return sensor is needed for return temperature limitation. Set the room group’s “function“ to “Primary controller + return sensor“. 24 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
If there is a request for DHW, the room group pumps are not put into operation. For this reason, DHW must from a hydraulics point of view always be installed upstream of the room groups. 25 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Specify if a DHW charging pump or DHW diverting valve is used and how it is controlled. Main menu > Commissioning > Basic configuration > DHW > DHW pump/valve: 26 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Enter the corresponding settings (e.g. DHW zone and time switch slave) on the unit with connected DHW heating (e.g. controller for heat generation). For more detailed information, see the technical documentation of the respective product. 27 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Control of scene-compatible switching, dimming and blinds devices plus RF adapter plugs KRF96... Info For direct selection of info pages via the softkeys; only available with switching groups 1 – 4. 29 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Activate communication with the Synergyr unit by setting Synergyr to "Active": Main menu > Commissioning > Basic configuration > Meter > Synergyr: Inactive – no Synergyr unit available (factory setting). Active Communication with Synergyr unit active. 31 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
> Meter > Heat/cooling energy > Heat/cool X > Source: Enter the desired metering medium. Main menu > Commissioning > Basic configuration > Meter > Heat/cooling energy > Heat/cool X > Metering medium: 32 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
A cold water meter is activated as soon as the source is set to unequal "---". Main menu > Commissioning > Basic configuration > Meter > Cold water > Cold water X > Source: 33 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
A meter is activated as soon as the source is set to unequal "---". Main menu > Commissioning > Basic configuration > Meter > Other > Other X > Source: 34 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 35 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
> Faults > Display fault bus: Only the controller-internal faults result in fault status messages (factory setting). Both controller-internal faults and faults received via bus result in fault status messages. 36 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Relay output Qx of an RRV91… heating circuit control- ler or RRV934 multi-controller used as a fault output. Q1 (local) Relay output Q1 of the central apartment unit used as a fault output. 37 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 38 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 39 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
By closing a contact at the input terminal, the respective input function can be triggered. Activate the respective input function by stating from where the central apart- ment unit receives the signal of the input terminal (Via RF/S-mode, B (local)). 40 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
B of the central apartment unit. * Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 41 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
KNX TP1 via commissioning tool (ETS). For the cooling function to become active when the input terminal closes, parameter ”2-pipe heating/cooling system“ must be activated (setting ”Yes“, see page 49). 42 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Specify if an external absence contact is used and from where the central apartment unit receives its status. Main menu > Commissioning > Basic configuration > Inputs > Absence: 43 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Configure outputs Outputs can transmit signals to external components. Activate the required output function by defining how the central apartment unit delivers the signal (via RF, Q1 (local)). 44 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Specify if a refrigeration demand relay is used and how it is controlled. Main menu > Commissioning > Basic configuration > Outputs > Refrig demand relay: 45 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 46 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
To release the exhaust hood, at least one of the windows in the selected rooms must be open, thus making certain that operation of the exhaust hood does not produce underpressure in the room. 47 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Specify if the business card (info page) should be displayed. Main menu > Commissioning > Basic configuration > Info pages > Business card: Do not show info page (factory setting). Show info page. 48 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Main menu > Commissioning > Basic configuration > Miscellaneous > 2-pipe H/C system: No 2-pipe system heating/cooling available (factory setting). 2-pipe heating/cooling system available. 49 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
* Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 50 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
KNX TP1 *. * Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 51 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
B of the central apartment unit. * Connection of the respective S-Mode objects of the central apartment unit to the relevant S-Mode de- vices on KNX TP1 via commissioning tool (ETS). 52 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
(Q4/Q5) of an RRV934 multi-controller. Meters The values to be set in the extra configuration for each meter are described in detail in the following sections. 53 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
(Menu/ok button) or to cancel the setting (Esc button). Impulse sensor type When connecting meters, use the impulse input to set the type of impulse sensor type. 54 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
8 8 8 8 8 8 8 8 The setting range for the unit factor is limited to meaningful values and depends on the meter type or medium. 55 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
> Meter > … > P'valency num: Main menu > Commissioning > Extra configuration > Meter > … > P'valency denom: Factory setting P'valency num P'valency denom 56 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Meter connected to the pulse input of the WRV8x or WRI80 to be replaced. Meter 3 Meter connected to the 1st pulse input of the 1st pulse adapter AEW2.1 of the apartment. 57 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Fault contact connected to universal input B of the central apartment unit. * Connection of the respective S-mode objects of the central apartment unit to the relevant S-mode de- vices on KNX TP1 via commissioning tool (ETS). 58 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Confirm entry on submenu “Connect device“ by pressing the Menu/ok button. To connect, the system asks you to press the binding button on the device to be connected. 59 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Release the button. F = Function button The binding symbol on the display of the room unit blinks and goes out after successful binding with the central apartment unit. 60 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
As soon as the actuator is ready for connection, the LED starts to blink green. Prior to connecting, the actuator must be fitted to a valve to ensure calibration is possible (error message). 61 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
The heating circuit controllers are automatically switched on as soon as power is applied. The LEDs are tested. All LEDs light up for one second. The mains LED lights up when the unit is ready to operate. 62 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Page 63
2 to 3-position. Switching between NC and NO works for previously connected heat- ing circuit controller channels. 63 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Main menu > Commissioning > RF connections > Smoke detector > Room X > Connect device: 64 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
= LEDs for 0..10 V universal output channels = LEDs for universal input channels = LEDs for universal relay output channels The multi-controller is connected by channel or channel group. 65 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
> Cooling release output > Room X > Connect device: Confirm subentry “Connect device“ by pressing the Menu/ok button. Activate binding mode from one of the following devices or device channels: 66 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
> Room group X > Return temperature sensor > Connect device: The following device channels can be connected: • Universal input Xx of a multi-controller (see page 65). 67 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Inform the central apartment unit that you want to connect an input for fire- place mode: Main menu > Commissioning > RF connections > Ventilation > Inputs > Open fireplace mode > Connect device: 68 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Press the binding button on the multi-controller. The LED lights up green. Re- lease the button when the LED starts blinking. Successful connection is displayed on the central apartment unit and con- firmed with a beep. 69 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
The following device channels can be connected: • Universal relay output Qx of a heating circuit controller (see page 62). • Universal relay output Qx of a multi-controller (see page 65). 70 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
The binding LED on the device blinks green and goes out on successful bind- ing with the central apartment unit. To confirm successful connection, the central apartment unit beeps. The device is now connected and performs normal operation. 71 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
GAMMA wave products. Connect switching group relay (QAX913 only) Inform the QAX913 central apartment unit that you want to connect an output as switching group relay: 72 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
= LED and function button to test connection, for binding and factory setting CH = Channel selection button = LEDs for pulse input channels = LEDs for M-bus channels 73 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Inform the QAX913 central apartment unit that you want to connect a fault in- put: Main menu > Commissioning > RF connections > Faults > Fault input X (1 – 8) > Connect device: 74 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
The following device channels can be connected: • Universal relay output Qx of a multi-controller (see page 65). • Universal relay output Qx of a heating circuit controller (see page 62). 75 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
• Universal relay output Qx of a multi-controller (see page 65). • Universal relay output Qx of a heating circuit controller (see page 62). • RF adapter plug KRF960 (see page 72). 76 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
LED starts blinking. Successful connection is displayed on the cen- tral apartment unit and confirmed with a beep. Press the Menu/ok button to exit the binding process. 77 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
The following device channels can be connected: • Universal input B of a heating circuit controller (see page 62). • Universal input Xx of a multi-controller (see page 65). 78 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
The following device channels can be connected: • Universal input U of a heating circuit controller RRV912 (see page 62). • Universal output U of a multi-controller (see page 65). 79 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
The following device channels can be connected: • Universal relay output Qx of a heating circuit controller (see page 62). • Universal relay output Qx of a multi-controller (see page 65). 80 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Switching groups are inputs from the configuration device TX100 perspective. To provide these inputs to the configurator and to assign a number, select the respective switching group on the central apartment unit and press the Menu/ok button: 81 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
If the binding process with the central apartment unit was unsuccess- ful, blinking of the LED changes to flashing after 1 minute (status indi- cation of unbound operation). 82 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Press the button on the respective GAMMA wave devices for at least 10 sec- onds. The central apartment unit beeps to confirm successful connection. For detailed information on commissioning the GAMMA wave compo- nents, see the documentation on GAMMA wave products. 83 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
The RF adapter plug state, however, can be switched over any time using the local button on the RF adapter plu. The wiring test for the different inputs and outputs is available in the following menus: 84 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Page 85
Outputs (heat demand relay, heat demand DC 0..10 V, refrigeration demand relay, refrigeration demand 0..10 V, summer operation, cooling enable, win- dow/door state, exhaust hood): Main menu > Commissioning > Wiring test > Outputs > … 85 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
The change of meter is also noted on the billing file. Adjusting the pulse sensor type is not recorded as change of meter. 87 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
> Room groups > Room group X > … > Device list: Main menu > Commissioning > RF connections > Ventilation > Inputs > … > Device list: 88 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
In addition, device number, device type and the KNX-ID of the individual de- vices are displayed also. Main menu > Commissioning > Device list > Device X: Press the Menu/ok button to display detailed device data. 89 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
KNX connection to the central apartment unit's bus supply. If several or other devices are connected to the bus, you must switch off the bus power supply by the central apartment unit. 90 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
> Time of day/date > Rem set clock slave: Clock time and date cannot be adjusted on the clock time slave. Clock time and date can be adjusted on the clock time slave. (Factory setting). 91 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
When operating external DHW heating, set the DHW zone of the central apartment unit to the same value as with external DHW heating. Main menu > Commissioning > Bus communication > DHW > Time switch op: 92 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system...
Outside temperature and atmospheric pressure zone Heat distr.zone Refrig.distr zone The zone settings must be unambiguous. For example, only one out- side sensor may have outside temperature zone 1 assigned. 93 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
When you confirm this message by Caution! pressing the Menu/ok button, the plant Plant starts starts operation according to the new settings and the display returns to the ”Main menu”. 94 / 134 Siemens Synco™ living CE1C2740en Building Technologies Commissioning the system 13.12.2010...
Main menu > Apartment > Settings > Setpoint limitation: Disabled Setpoint limitation is disabled. Enabled Setpoint limitation is enabled (factory setting). 95 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
The Economy room setpoint for heating all rooms is increased depending on the composite outside temperature. The increase at low outside temperatures (e.g. end point -15 °C) is greater and negated at higher outside temperatures (e.g. starting point -5 °C). 96 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
The proportion of the individual sensors cannot be changed. Main menu > Rooms > Room X > Room settings > Proportion room unit: Factory setting 50 % 97 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
They are enabled again only when the changeover locking time has elapsed. Main menu > Rooms > Room X > Room settings > H/C changeover lock: Factory setting 00:00 98 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
For your guidance, see the default settings (factory setting 5400 s): Room type Guide value Tn Radiator heating slow 5400 s Radiator heating fast 3600 s Floor heating slow 7200 s Floor heating fast 5400 s 99 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
For your guidance, see the default settings (factory setting 0.8 K): Room type Guide value switching differential Radiator heating slow 0.8 K Radiator heating fast 0.8 K Floor heating slow 0.8 K Floor heating fast 0.8 K 100 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
Using this function, a minimum flow temperature can also be guaranteed for uncontrolled rooms. In combination with “Min valve position Comfort“, cold floors can thus be prevented. 101 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
Page 102
Use the arrow button to go to the set- ting for curvepoint 2. The setting pro- cedure is the same as that with curvepoint 1. 102 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
> Limitations space heating > Return temp min: Factory setting Main menu > Room groups > Room group X > Limitations space heating > Return temp max: Factory setting 103 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
The five curvepoints of the cooling curve are set analogous to the min. flow heating setpoint (see page 101): If not needed, deactivate curve- Cooling curve points 3 to 5 by setting the outside temperature to "---". 104 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
Specifies the validity of a heat request for room heating from a room group during winter operation: Main menu > Room groups > Room group X > Settings > Temp request winter: 105 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
You can set the primary controller’s P-band Xp for each room group depend- ing on demand (1..100 K). Main menu > Room groups > Room group X > Primary controller > P-band Xp: Factory setting 50 K 106 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
The controller’s P-band (0..2000 ppm) can be set here. Within this range, all available stages are switched on and off. Main menu > Ventilation > IAQ controller > P-band Xp: Factory setting 400 ppm 107 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
Running time humidity limitation The humidity limitation interval starts with the running time set here (0..720 min). During this period of time, the ventilation system operates at the preselected stage. 108 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
Select the reference room to indicated to the controller which of the room sen- sors is the most suited for acquiring the reference value. Main menu > Ventilation > Night cooling > Reference room: Factory setting Room 1 109 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
(00.00..60.00 mm.ss) starts. The next lower stage is switched on only when this time has elapsed. Main menu > Ventilation > Ventilation settings > Rundown time: Guide value 00.00 mm.ss 110 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
Legionella protection period When the legionella function is active, the DHW storage tank is maintained at the legionella protection setpoint for the period of time set here (0.00 – 6.00 hours). 111 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
(5..250 min). Setting “---“ charges DHW with no limitation of the charging time. Main menu > DHW > Settings > Charging time max: Factory setting 60 min 112 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
To allow for DHW charging, the flow temperature must be higher than the re- quired DHW setpoint. Set the required setpoint boost here (0..50 K). Main menu > DHW > Settings > Setp incr DHW charg: Factory setting 10 K 113 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
For control of the electric immersion heater in the summer, the controller gives consideration to the time switch and the holiday program (factory setting). DHW operating mode must be set to ”Auto“. 114 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
The following information is displayed at the expert level for each meter. Consumption data of general meters (allocation = general) are visible only at the expert level. 115 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
As a result of the dates set for the change from standard to daylight saving time, or vice versa, the time of day on the first Sunday after that date is ad- 116 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
The measured value of the connected outside sensor is forwarded to other controllers on the same bus. Main menu > Inputs/outputs > Inputs > OT simulation: Factory setting --- (no simulation) 117 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
Main menu > Settings > Texts > Business card > BC line 1 – 4: Meter names Assign clear names to the meters (e.g. kitchen, bathroom, etc.). Main menu > Settings > Texts > Meter > …: 118 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
Main menu > Settings > Heat request > Temp request thresh: Factory setting Temp request at 0 V 0 °C Temp request at 10 V 100 °C Temp request threshold 0 °C 119 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
Main menu > Settings > Refrigeration request > Temp request thresh: Factory setting Temp request at 0 V 35 °C Temp request at 10 V 10 °C Temp request threshold 25 °C 120 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings 13.12.2010...
From the current software and memory data (software version, EEPROM data, flash data) an unambiguous “Valid Version Set-ID” is produced. This enables Siemens to unambiguously identify the software status of a cen- tral apartment unit e.g. when a problem occurs.
When restoring data, certain bus settings and all set texts are not overwritten and are retained with their present state. When restoring the factory settings, customized texts are also reset. 122 / 134 Siemens Synco™ living CE1C2740en Building Technologies Function settings...
Radiator control actuators (one lead controller, 0…5 lag controllers) or heating circuit controller channels Window contacts Smoke detector (QAX913 only) Radiator control actuators and heating circuit controllers cannot simul- taneously be used in the same room. 123 / 134 Siemens Synco™ living CE1C2740en Building Technologies System limits 13.12.2010...
Manual control of the radiator control actuator For service work, or in the event of 3 mm fault, the SSA955 can be brought into any position using a 3 mm hexagon socket wrench. 124 / 134 Siemens Synco™ living CE1C2740en Building Technologies Communication 13.12.2010...
Comply with local and currently valid legislation. Dispose of ex- hausted batteries in compliance with relevant environmental regula- tions. 125 / 134 Siemens Synco™ living CE1C2740en Building Technologies Disposal 13.12.2010...
Charging time max ....112 Consumption data interface..73 Clock time operation ....91 Dew point......79 Comfort valve position....98 Fault input......74 Commissioning....18, 20 Fault output......75 Commissioning Exit....94 Fireplace contact ....68 126 / 134 Siemens Synco™ living CE1C2740en Building Technologies Index 13.12.2010...
Page 127
Door/window contact....64 Connect......78, 81 Due date........54 Cooling enable DC 0..10 V Connect........ 80 Cooling/heating ......42 Economy increase....96 Electric immersion heater..27 Enabel setpoint limit....95 127 / 134 Siemens Synco™ living CE1C2740en Building Technologies Index 13.12.2010...
Page 128
Heat request DC 0..10 V ..119 Heat request Threshold value . 119 Heating circ. controller RRV..62 Knockout holes ......14 Heating setpoint limitation ..96 KRF960, KRF961 ....72, 83 128 / 134 Siemens Synco™ living CE1C2740en Building Technologies Index 13.12.2010...
Page 129
Precontroller ....... 106 Room........21 Room controller ....99 Room group ....22, 118 P-band Xp IAQ ....... 107 Neutral zone room controller.. 100 P-band Xp indoor air quality... 107 129 / 134 Siemens Synco™ living CE1C2740en Building Technologies Index 13.12.2010...
Page 130
Gas shutoff valve....39 Setpoint Heat demand......45 Boost DHW......113 Refrigeration demand... 45 Decrease mixing valve ..105 Status ........40 Increase mixing valve ..105 Summer operation....46 Legionella protection ..111 130 / 134 Siemens Synco™ living CE1C2740en Building Technologies Index 13.12.2010...
Page 131
Temperature display ....36 Temperature request ..... 106 Winter operation....105 Zone Test DHW........92 Radio connections ....84 Distr........93 Water detector....121 Outside temperature..... 93 Wiring ........84 131 / 134 Siemens Synco™ living CE1C2740en Building Technologies Index 13.12.2010...
Page 132