Siemens Desigo RXB Technical Manual page 67

Technical manual
Table of Contents

Advertisement

Connection terminals
RXB24.1
Caution
Tool socket
Siemens
Building Technologies
1
2
3
4
5
6
7
T
AC 230V
19 19 21 21
Measured value input
B1
1
Measured value input for LG-Ni 1000 sensors
M
2
Measured value input ground
Signal inputs
D1
4
Signal input
GND 5
Signal ground
D2
6
Signal input
Triac outputs
Y1
7
AC 24 V, 0.5 A switching output
G
8
AC 24 V actuator supply
Y2
9
AC 24 V, 0.5 A switching output
Y3
10
AC 24 V, 0.5 A switching output
G
11
AC 24 V actuator supply
Y4
12
AC 24 V, 0.5 A switching output
Room unit
CP–
13
PPS2 ground
CP+
14
PPS2 data
CE+
15
KNX / EIB data cable
CE–
16
KNX / EIB data cable
KNX / EIB bus (plug-in connection)
CE+
17
KNX / EIB data cable
CE–
18
KNX / EIB data cable
Power supply
N
19
Neutral conductor
R
21
Phase conductor AC 230 V +/- 10 %
 Local installation regulations must be observed.
Proprietary RJ45-type tool socket
1 KNX / EIB data cable (CE+)
1 2 3 4 5 6 7 8
2 KNX / EIB data cable (CE–)
3 Not used
4 Not used
RXB24.1 – Room controller
8
9
10 11 12 13 14 15 16
2
1
4
QAX...
M
M
17 18
EIB / KNX
3
5 +12VDC
6 RxD
7 PPS2 (CP+) / TxD
8 PPS2 (CP–)
CM2N3874en_04
11 / 16
02 Apr 2010