HandyTool See the parameters in the last column of the following table.
Parameter for downdraft
compensation
Outside temp 0% valve pos
Outside temp max valve pos
Maximum valve pos
Enable the function
86/140
Siemens
Building Technologies
Select Sequences, Other setpoints:
Select Sequences , Other setpoints:
Basic
setting
0 °C
–10 °C
100%
The following conditions must be fulfilled:
– The room controller must be in Comfort room operating mode.
RXB (KNX) Applications library
Control sequences
Range
Resolution
–30 ... 10 °C
0.5 K
–30 ... 10 °C
0.5 K
0 ... 100%
1%
CLC and RAD description of functions for CC-02 CM110384en_03
Parameter
HandyTool
*078
*079
*080