Address Zones In Lte Mode (Together With Synco) - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

ACS Service
HandyTool
*006 Communication mode
Siemens
Building Technologies
The ACS service tool is used in Synco networks.
It has access to LTE mode only.
Setting
0
1
3.1
Address zones in LTE mode
(together with Synco)
This section applies only to LTE mode.
Zone addresses must be allocated in cases where RXB Konnex controllers are used in
LTE mode (e.g. together with Synco). These must be defined together with the Synco
devices at the planning stage.
The zones to be defined are:
Geographical zone
(Apartment . Room . Subzone)
Apartment = ---, 1...126
Room
= ---, 0...63
Subzone
= ---, 0...15
Time switch zone
(Apartment . Room . Subzone)
Apartment = ---, 1...126
Room
= ---, 0...63
Subzone
= ---, 0...15
Refrig distr zone cooling
surface
Zone
= ---, 1...31
Heat distr zone heating
surface
Zone
= ---, 1...31
RXB (KNX) Applications library
Select communications mode
Mode
S-mode
LTE and S-mode
Zone in which an RXB Konnex controller is located.
Other room-specific devices may also be located in this
zone.
The designations "Apartment, Room and Subzone do
not need to be taken literally. For example, Apartment
can be used to refer to a group of rooms, floor, or
section of a building.
Room, however, really does refer to a room..
Subzone is unlikely to be used much for HVAC devices
– it is more relevant to other disciplines such as lighting
(keep the setting 1).
This zone has the same structure as the geographical
zone. It indicates the source of the schedule for the
RXB Konnex controllers.
The same zone must also contain a device to provide
the schedule (e.g. a Synco RMx7xx or RMB795).
In a Synco network, Room and Subzone must always
be set to 1.
Chilled water-specific information of a chilled ceiling is
exchanged within this zone (e.g. cooling demand). This
zone also includes a Synco device to process the
information (e.g. RMU7xx or RMB7xx).
Hot water-specific information of a radiator is
exchanged within this zone (e.g. heating demand). This
zone also includes a Synco device to process the
information (e.g. RMU7xx or RMB7xx).
CLC and RAD description of functions for CC-02 CM110384en_03
21/140
28 Feb 2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents