• The M/S function presupposes that all 3 M/S zones match.
• If the master/slave function is not required, the M/S zone should be disabled (to limit
the load on the bus).
Parameter
Short name
*021
Master/Slave
*022
M/S zone (apartm)
*023
M/S zone (room)
*024
M/S zone (subzone)
Parameter
*021 Master/Slave
9.2.1

Window switch (LTE mode)

For master/slave mode, only the master's window switch is evaluated without special
measures, which also influences the slave controllers.
Window switches on the slaves are NOT considered.
9.2.2

Presence detector (LTE mode)

For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
Presence detectors on the slaves are NOT considered.
9.2.3

Dewpoint sensor (LTE mode)

For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
Window switches on the slaves are NOT considered.
RXB (KNX) Applications library
Master/slave
Setting
Master
Slave
CLC and RAD description of functions for CC-02 CM110384en_03
Basic setting
Master
1
–1 (out of service)
1
HandyTool
1
0
28 Feb 2009