Bus supply for RXB Konnex controllers

RXB controllers work without bus supply if the following conditions are adhered to:
• Parameterize only using the Handy Tool (not with ETS3 or ACS).
• No integration in a building automation and control system (e.g. DESIGO, Synco).
• No changeover operation (sensor signal via bus).
• No outdoor temperature via bus.
• No master/slave combinations.
Else, the Konnex bus, used by RXB room controllers for communications, requires a
bus supply.
Each controller consumes 5 mA. Thus, select the supply according to the number of
controllers. We recommend the following products:
Manufacturer
Siemens Building Technologies
Siemens Automation and Drives
1.7

RXB Konnex controller communications

The RXB Konnex controllers support communications as defined in the Konnex
specification.
This specification defines the following modes among others:

• S-mode

= Standard mode.
• LTE-Mode= Logical Tag Extended Mode
This is a new mode which supports simpler engineering and is used
with Synco.
1.7.1
S-mode
This mode corresponds to EIB communications. Connections are established via ETS3
Professional and group addresses.
This ensures a link to the existing EIB environment.
Refer to the EIB manual for more information on this mode.
RXB (KNX) Applications library
Introduction
Type
ACX95.320/ALG
5WG1 125-1AB01
5WG1 125-1AB11
5WG1 125-1AB21
CLC and RAD description of functions for CC-02 CM110384en_03
Designation
Power supply 320 mA
Power supply 160 mA
Power supply 320 mA
Power supply 640 mA
7/140
28 Feb 2009