Siemens Desigo RXB Technical Manual page 433

Technical manual
Table of Contents

Advertisement

Two-pipe fan coil with changeover and outside
air damper
Plant diagram
N1
Room controller.
R1
Room unit with temp.
sensor.
B1
Return air sensor.
B2
Outside air temperature
sensor via KNX bus.
D1
Window switch.
D2
Presence detector.
D3
Changeover signal via KNX
bus.
D4
Safety thermostat, outside
air.
Q1
Fan (1... 3-speed).
YHC Heating/cooling valve.
YM
Outside air damper.
Operating diagrams
Y
Output signal.
TR
Room temperature.
TO
Outside air temperature.
SpH
Effective heating setpoint.
SpC
Effective cooling setpoint.
SpEcm Economizer setpoint.
SpFr
Risk of frost limit
H
Heating sequence.
C
Cooling sequence.
YHC
Heating/cooling valve.
YM
Outside air damper.
Q14
Fan speed 1.
Q24
Fan speed 2.
Q34
Fan speed 3.
Siemens
Building Technologies
Heating only (with LTHW), cooling only (with CHW) or changeover.
Changeover signal via KNX bus.
Modulating control of heating/cooling valve.
Outside air damper for outside air supply.
Outside air temperature sensor via KNX bus.
Automatic or manual fan control.
D3
YHC
YM
D4
M
N1
K N X
R
Y [%]
Change-over
H
100
YHC
YHC
0
SpH
SpC
Change-over
Y
H
Q34
Q24
Q14
SpH
SpC
RXB application library (KNX)
FNC10 – Two-pipe fan coil with changeover and outside air damper
Q1
T
B1
T
R1
D1
Y [%]
C
100
min
0
TR [°C]
C
TR [°C]
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12
FNC10
K NX
B2
D2
YM
TO [°C]
SpFr
SpC
SpEcm
CM110672en_03
30.11.2007
R
31/52

Hide quick links: