Central And Local Control Of Room Operating Mode Based On Occupancy - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

K N X
CO
R
Occupancy schedule
Presence detector
36/140
Siemens
Building Technologies
The following S-mode communication object is used for schedule usage from a building
automation and control system:
Time schedule Use (input communication object)
Flags
Type
R W C T U
0 1 1 0 0 20.002
DPT_BuildingMode
5.3.3
Central and local control of room operating mode
based on occupancy
Central
Local
Controller
Prio
S
1.
DI
2.
S
3.
S
S
DI
3.
PPS2
3.
S
The central time schedule transmits the anticipated occupancy of a room or group of
rooms. It controls the room operating mode of a room controller while the building is in
use. Outside the building-in-use period, the time schedule is disabled.
The time schedule can be used, e.g. by a building tenant to specify occupancy times of
his or her rooms.
The occupancy schedule has three possible states:
State
Description
• Occupancy expected.
Occupied
• Room controller switches to Comfort.
• Occupancy is probable; the room must be ready for use shortly
Standby
( Comfort temperature).
• Room controller switches to Precomfort.
• No occupancy expected.
Unoccupied
• Room controller switches to Economy.
A presence detector detects the presence of people in a room.
It controls the room operating mode of a room controller while the building is in use.
Outside the building-in-use period, it is disabled.
RXB (KNX) Applications library
Room operating modes
Receive timeout
Yes
The Effective occupancy is determined by the
occupancy schedule and the presence detector.
S
It controls the room operating mode of a room
controller while the building is in use.
S
CLC and RAD description of functions for CC-02 CM110384en_03
States
0 = In use
1 = Not in use
2 = Protection
28 Feb 2009