Time schedule
Room operating
mode
Room with room unit
/Auto button
on the room
unit Room 1
Effective
Room operating
mode
Room 1
Room with presence
detector
Presence detector
Room 2
Effective
Room op. mode
Room 2
Siemens
Building Technologies
• The occupant(s) of Room 1 are working overtime. At 18.00 hours the room operating
mode changes to Economy , even if the room unit is set to Auto (1).
Comfort mode can now be re-activated with the Auto switch on the room unit (2).
Comfort remains active for the pre-defined Temporary Comfort mode period (see
page 126).
In Protection mode however, the Temporary Comfort period is also overridden and
the room operating mode changes to Protection (3).
• In Room 2, in the evening, there are still people in the room beyond the "building-in-
use" period (4). However, at the end of the building-in-use period the room operating
mode still changes to Protection. An alarm can also be tripped, if required.
Comfort
Precomfort
Economy
Protection
Auto
Comfort
Precomfort
Economy
Protection
Occupied
Unoccupied
Comfort
Precomfort
Economy
Protection
RXB (KNX) application library
Room operating modes
06:00
08:00
FNC Description of functions for FC-10, FC-11, FC-12
10385D05
18:00
20:00
1)
3)
2)
1)
2)
3)
4)
4)
63/166