Siemens Desigo RXB Technical Manual page 51

Technical manual
Table of Contents

Advertisement

Connection terminals
RXB21.1
Caution
Tool socket
Siemens
Building Technologies
1
2
3
4
5
6
7
T
AC 230V
19 19 21 21
Measured value input
B1
1
Measured value input for LG-Ni 1000 sensors
M
2
Measured value input ground
Signal inputs
D1
4
Signal input
GND 5
Signal ground
D2
6
Signal input
Triac outputs
Y1
7
AC 24 V, 0.5 A switching output
G
8
AC 24 V actuator supply
Y2
9
AC 24 V, 0.5 A switching output
Y3
10
AC 24 V, 0.5 A switching output
G
11
AC 24 V actuator supply
Y4
12
AC 24 V, 0.5 A switching output
Room unit
CP–
13
PPS2 ground
CP+
14
PPS2 data
CE+
15
KNX / EIB data cable
CE–
16
KNX / EIB data cable
KNX / EIB bus (plug-in connection)
CE+
17
KNX / EIB data cable
CE–
18
KNX / EIB data cable
Power supply
N
19
Neutral conductor
R
21
Phase conductor AC 230 V +/- 10 %
Relay outputs
Q13
25
Common feed for Q14, Q24 and Q34
Q14
26
Normally-open contact, max. AC 250 V, 5 (4) A (Stage 1)
Q24
27
Normally-open contact, max. AC 250 V, 5 (4) A (Stage 2)
Q34
28
Normally-open contact, max. AC 250 V, 5 (4) A (Stage 3)
Observe the technical data for the relay outputs: max. AC 250 V, 5 (4) A
Local installation regulations must be observed.
Proprietary RJ45-type tool socket
1 KNX / EIB data cable (CE+)
1 2 3 4 5 6 7 8
2 KNX / EIB data cable (CE–)
3 Not used
4 Not used
RXB21.1, RXB22.1 Room controllers
8
9
10 11 12 13 14 15 16
2
1
4
QAX...
M
M
AC 230V 5(4)A
25 26 27 28
17 18
EIB / KNX
3
5 +12VDC
6 RxD
7 PPS2 (CP+) / TxD
8 PPS2 (CP–)
CM2N3873en_06
11/16
02 Apr 2010