8.3
Fan coils with an electric heating coil
This function will be implemented later.
8.4
Fan coils with an electric reheater
In addition to controlling heating and/or cooling valves, some applications also provide
an output for the control of an electric heating coil. This is then operated as a reheater ,
i.e. it only comes into operation when the heating valve is fully open.
• With motorized actuators, the electric reheater is only enabled when the heating
valve is fully open.
• In the case of thermal actuators, the electric reheater is not enabled until the thermal
actuator has been operated at maximum flow (100%) for at least 2 minutes.
• The switching differential is fixed at 1.0 K.
8.4.1
4-pipe fan-coils with electric reheater
YR
YC
YH
1-step
YR
Y
1 K
H
100%
ON
0%
OFF
RXB (KNX) application library
Control sequences
D3
Q1
T
B1
YH
YC
TR [°C]
SpH
SpC
FNC Description of functions for FC-10, FC-11, FC-12
Y
Output signal
TR
Room temperature
SpC
Effective cooling setpoint
SpH
Effective heating setpoint
H
Heating sequence
C
Cooling sequence
YH
Heating valve
YC
Cooling valve
YR
Electric reheater
D3
Safety thermostat
B1
Return air sensor
Q1
Fan
Modulating
YR, Y
H
100%
YR
YH
0%
SpH
SpC
CM110385en_05
YC
TR [°C]
95/166