Test The Periphery Using Room Unit Qax34.3 - Siemens Desigo RXB Technical Manual

Technical manual
Table of Contents

Advertisement

Prerequisite
Theoretically possible positions for periphery testing:
T 01
Sensor input B1
T 11
Digital input D1
Digital input D2
T 12
T 21
Heating valve
1) 2) 7)
Cooling valve
T 22
Heating surface
T 25
6)
T 51
Triac Y1
6)
T 52
Triac Y2
6)
Triac Y3
T 53
6)
T 54
Triac Y4
18/140
Siemens
Building Technologies
2.7

Test the periphery using room unit QAX34.3

This function requires a QAX34.3 with index D or higher!
The HandyTool allows you to test the connected field devices (sensors, actuators).
This works only for the controller connected to the HandyTool; master/slave operation
is not possible.
An application must be selected and fully parameterized in the controller (address
and zones can contain default values).
Start parameterization mode:
• Press buttons < , > and – simultaneously for about 2 s until the display turns dark.
• Release the buttons.
• Press button – twice briefly.
• Press buttons + and – simultaneously for approx. 2 s
• Press button + twice briefly.
The display now shows
Use + and / or – to choose between the following modes:
0 =
Normal mode (normal room unit functions).
1 =
Test mode
2 =
Display mode (see 2.5.2).
3 =
Parameterization mode (see 2.5.2).
4 =
Upload (see 2.6).
5 =
Download (see 2.6).
6 =
Service mode.
The following positions can be selected depending on the type of parameterization.
They are displayed with prefix "T".
The list shows all theoretically possible positions. However, only positions that are
available for selection based on the type of parameterization are displayed.
9)
Value of B1 in °C.
9)
True state of the contact at D1 (0 = open; 1 = closed).
9)
True state of the contact at D2 (0 = open; 1 = closed).
1) 2) 7)
By considering the configuration (proportional; 100 = 100% pos. signal).
By considering the configuration (proportional; 100 = 100% pos. signal).
1) 4) 7)
By considering the configuration (proportional; 100 = 100% pos. signal).
(0 = Triac disabled; 1 = enabled).
(0 = Triac disabled; 1 = enabled).
(0 = Triac disabled; 1 = enabled).
(0 = Triac disabled; 1 = enabled).
1)
Considering the configuration means:
– For thermal actuators, the output is clocked 1:1 during the first 400 s, then as per
the % entry.
– Motorized actuators open at 100% 1.5 times the runtime, and close at 0% 1.5
times the runtime.
RXB (KNX) Applications library
Definitions / Tools
0 (mode 0).
CLC and RAD description of functions for CC-02 CM110384en_03
The display goes dark.
28 Feb 2009