ETS3 Professional
ACS Service
HandyTool See the parameters in the last column of the following table.
Notes
Siemens
Building Technologies
Select tab General functions, Temperature sensor B1 (see page 100).
Select General functions, Temperature sensor r B1 (see page 100).
Short name
Temperature sensor B1
Room
Only meas val acquisition
No sensor
Only meas val acquisition: Use of the signal: see "analog input B1", page 112.
7.1.3
Averaging analog input & PPS2 interface
In large spaces it can be useful to measure the room temperature in two locations and
to determine an average value. If both a QAX3... room unit and a QAA24 LG-Ni1000
sensor are connected to a controller, the measured room temperature is automatically
based on the average value from both sensors. Automatic detection prevents
miscalculation.
A QAX34 / QAX84 will display this average value.
QAA24
B1
PPS2 (CP+, CP-)
RXB2...
The average value is calculated from the two sensor readings.
• To determine the average value, the sensor must be configured as a room
temperature sensor
• There is no averaging in KNX sensors.
7.1.4
Sensor correction
The value of the local sensors (PPS2 and B1) can be corrected in the tools
(see page 115).
RXB (KNX) Applications library
Temperature measurement
Basic setting
No sensor
QAX3...
CLC and RAD description of functions for CC-02 CM110384en_03
Parameter
*092
1
3
255
75/140
28 Feb 2009