Siemens Desigo RXB Technical Manual page 234

Technical manual
Table of Contents

Advertisement

Configuration
Menu
Communication
Room temperature setpoints
Other setpoints
Sequences
LTE mode
Motorized and electromechanic Runtime
Motorized Offset
Room unit
With LCD Display heating/cooling symbols
General functions.
Central functions
Master/slave
14/16
Siemens
Building Technologies
The following parameters are available with application CLC02.
They are set via ETS, ACS, or HandyTool.
Parameters.
Communication mode
Receive timeout
Send heartbeat
Protection cooling setpoint
Economy cooling setpoint
Precomfort cooling setpoint
Comfort cooling setpoint
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
Protection heating setpoint
Downdraft compensation
Outside temp 0% valve pos
Outside temp max valve pos
Maximum valve pos
Actuator type cool surf valve
Actuator type heating surface valve
Cooling surface outp bus valve
Heating surface outp bus valve
Measured value correction
Setpoint offset range
Local Comfort mode
Room unit
Temperature unit
Standard display
Setpoint display
Digital input 1
Free (bus = 1)
Occupancy: Occupied
Window:
Dewpoint:
Digital input 2
Free (bus = 1)
Occupancy: Occupied
Window:
Dewpoint:
Temperature sensor B1
Temporary Comfort mode
On-delay occupancy detector
Off-delay presence detector
Heating demand signal
Cooling demand signal
Boost heating
Reset setpoint offset
Master/slave
RXB application library (KNX)
CLC & RAD – chilled ceiling and radiator applications from CC-02
CLC02 – Chilled ceiling and radiator
Values/Range
S-mode / LTE and S-mode
0 ... 105 min.
0 ... 105 min.
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
10 ... 40 °C
–30 ...10°C
–30 ...10°C
0 ... 100 %
– STA71
– STA72E
– STE71
– STE72
– STP71
– STP72E
– Motorized 3
rd
– Thermal 3
– Motorized bus
– STA71
– STA72E
– STE71
– STP71
– STP72E
– Motorized 3
rd
– Thermal 3
– Motorized bus
Off/On
Off/On
0 ... 360 s
0 ... 360 s
– 3 ... 3 K
± 0 ... 10 K
Enabled / Disabled
Without LCD / with LCD
Enabled / Disabled
°C or °F
No display / Room
temperature / Setpoint
Absolute / Relative
= Contact open/closed
= Contact open/closed
Window open
= Contact open/closed
Alarm inactive: = Contact open/closed
= Contact open/closed
= Contact open/closed
Window open
= Contact open/closed
Alarm inactive: = Contact open/closed
– Room
–Only meas val acquisition
– No sensor
0 ... 360 min
0 ... 90 min
0 ... 90 min
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Enabled / Disabled
Master or slave
Basic setting
S-mode.
60 min.
45 min.
40 °C
35 °C
28 °C
24 °C
21 °C
19 °C
15 °C
12 °C
0 °C
–10 °C
100 %
STA72E
– SSA81
– SSB81
– SSC81
– SSP81
– SQS81
rd
devices
devices
– SSA81
STP72E
– SSB81
– SSP81
– SQS81
rd
devices
devices
Off
Off
150 s
0 s
0 K
± 3 K
Enabled
Without LCD
Enabled
°C
Room temperature.
Relative
Free (bus = 1)
= Contact closed.
Free (bus = 1)
= Contact closed.
No sensor
60 min
5 min
5 min
Enabled
Enabled
Enabled
Disabled
Master
CM110671en_02
14.03.2008