K N X
CO
R
Parameter: Local Comfort mode
K N X
CO
R
Siemens
Building Technologies
The following LTE-mode communication object is provided for central control:
Enable Comfort (input)
Possible partner function blocks)
EnableComfort
110 HVACS
HVAC-Mode Scheduler
Timeswitch zone
104 PMC
Programs to HVAC-Mode Conversion
Possible states are:
State
Enabled
Disabled
Comfort and Precomfort are enabled locally in the controller with the following
parameter in the Room unit menu on page 114.
Description
Change from Economy to Precomfort or Comfort mode.
Enabled (basic setting)
Precomfort or Comfort can be disabled via the Enable
Comfort input.
Disabled (ignore Enable Comfort input). Precomfort or
Comfort CANNOT be disabled via the Enable Comfort
input.
5.5.3
Central control of room operating mode via
room operating mode input
Local
Central (ACS)
Controller
Prio
Central
(Synco controller)
DI
DI
PPS2
Room operating mode (input)
Possible partner function blocks)
110 HVACS
HVACMode
HVAC-Mode Scheduler
Timeswitch zone
104 PMC
Programs to HVAC-Mode Conversion
RXB (KNX) Applications library
Room operating modes
Description
Priority 3 influences ( room operating mode input,
presence detector, room unit) are enabled.
Priority 3 influences are disabled.
The effective room operating mode is Economy.
The following LTE mode communication object is used
to control the room operating mode from a building
0.
automation and control system:
1.
1.
2.
3.
3.
3.
CLC and RAD description of functions for CC-02 CM110384en_03
Known partner devices
Siemens:
Synco
RMB795
HandyTool
*105
1
0
Known partner devices
Siemens:
Synco RMU710 / 20 / 30
RMH760 / RMB795
57/140
28 Feb 2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Desigo rxc, desigo rxb, desigo rxl, desigo rxa

Table of Contents