Bytes 2-3: Starter State; Bytes 4-5: Trip Code - Danfoss VLT MCD 200 Installation Manual

Hide thumbs Also See for VLT MCD 200:
Table of Contents

Advertisement

PROFINET Module
Installation Guide
Bits
Details
0 = Auto on (Network).
1 = Hand on (LCP, Digital Input).
7
1 = Ramping (starting or stopping).
8
1 = Ready.
9
1 = Starting, running, or stopping.
10
1 = Tripped.
11
1 = Warning.
12–15
Reserved.
Motor current (% FLC) represents current as a percentage of the set motor full load current. A maximum value of 63 represents
200% full load current. To convert this value to a readable percentage, divide by 0.315.
7.3.2 Bytes 2–3: Starter State
Bits
Details
0–3
The decimal value of bits 0–3 indicates the state of the soft starter:
0 = Communication error between device and soft starter.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check).
6 = Tripped.
7 = Menu open (cannot start).
8 = Jog forward.
9 = Jog reverse.
4
0 = Negative phase sequence.
1 = Positive phase sequence.
5
1 = Current exceeds FLC.
6
0 = Uninitialized.
1 = Initialized.
7
1 = Communication error between device and soft starter.
8–15
Reserved.
7.3.3 Bytes 4–5: Trip Code
Bits
Details
0–15
See the chapter Trip Codes.
Danfoss A/S © 2022.11
Packet Structures
AN428735951761en-000101 / 175R1188 | 21