In normal operation the MCD 500 is controlled via a remote two wire signal (terminals 17, 18).
Input A (terminals 11, 16) is connected to an external trip circuit (such as a low pressure alarm switch for a pumping system). When the external circuit
activates, the soft starter trips, which stops the motor.
5
1
Control voltage (model dependent)
2
24 VDC output
3
Remote control inputs
4
Motor thermistor input (PTC only)
5
Relay outputs
6
3-phase supply
7
Motor terminals
Parameter settings:
•
Par. 3-3
Input A Function
•
Select Input Trip (N/O) assigns the Input A to Auxiliary Trip (N/O) function
Input A Name
•
Par. 3-4
•
Select a name e.g. Low Pressure - assigns a name to Input A.
•
Par. 3-8
Remote Reset Logic
•
Select as required e.g. Normally Closed - the input behaves like a normally closed contact.