Start/ stop profile setting table:
Start/stop
Start
Profile
Performance
Equivalent to
0
DOL
1
Fastest
2
|
3
|
4
|
5
|
6
|
|
7
|
8
9
Slowest
10
Fastest
11
|
12
|
13
|
14
|
15
Slowest
Note: * indicates Stop Ramp time is not controlled
by DMS. Motor will coast to stop.

Trip Class selection :

This setting is applicable only for the Extended
versions of DMS.
The DMS motor overload protection is an advanced
motor thermal model. Motor temperature is
continuously calculated by the microprocessor.
This uses a sophisticated mathematical model
to accurately reflect motor heat generation and
dissipation during all stages of operation, e.g.
Starting, Running, Stopping & Stopped.
Because it operates continuously, the motor thermal
model eliminates the need for protection systems such
as Excess Start Time, Limited Starts per hour etc.
Calibrate the DMS motor thermal model for theTrip
Class of the connected motor. The Motor Trip
Class is defined as the length of time the motor
can sustain Locked Rotor Current. The motor
Trip Class can be found from the motor curves
or data sheet. For example, if a given motor can
10
Stop
1
2 (A2) 3 (A3)
Performance
(A1)
Coast to stop
Off
Off
Off
Off
Off
Coast to stop
Off
Off
Off
On
On
Fastest
On
|
On
|
On
|
On
|
On
Slowest
On
DMS Manual
Initial
4
Voltage
(A4)
Off
Off
Off
Off
Off
On
Off
On
Off
Off
On
On
On
Off
Off
On
Off
On
On
On
Off
On
On
On
Off
Off
Off
Off
Off
On
Off
On
Off
Off
On
On
On
Off
Off
On
Off
On
On
On
Off
On
On
On
# In some applications, actual ramp time on the
motor shaft could differ from the settings.
withstand Locked Rotor Current for 10 sec, set
Trip Class 10 (or lower) in the DMS.
If in doubt, use "Trip Class 5", which is the Factory
Default setting for this parameter. With this setting,
the DMS will trip & protect the motor if the Locked
Rotor current sustains for more than 5 secs.
Use the DIP switches A5-A6 to choose the Trip Class.

Trip Class selection table :

Trip Class
5
6
Time
(A5)
(A6)
(sec)
5
Off
Off
10
Off
On
20
On
Off
0
On
On
MG.05.A2.02 - VLT is a registered Danfoss trademark
Start
Stop
Ramp
Ramp
Time
time
(%)
(sec) #
(sec) #
80
0.25
*
80
0.5
*
60
0.75
*
60
1.5
*
60
1.0
*
50
2
*
40
3
*
50
4
*
60
6
*
60
8
*
60
2
1
50
3
2
40
4
3
40
5
3
30
7
5
30
9
7
Remarks
Trip Class 5
Trip Class 10
Trip Class 20
Motor Protection off