PROFINET Card
Installation Guide
Bits
Details
9
1 = Starting, running, or stopping
10
1 = Tripped
11
1 = Warning
12–15
Reserved
6.3.2 Bytes 2–3: Starter State
Bits
Details
0–3
The decimal value of bits 0–3 indicates the state of the soft starter:
0 = Communication error between device and soft starter.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check, run simulation, reset input is open).
6 = Tripped.
7 = Menu open (cannot start)
8 = Jog forward.
9 = Jog reverse.
4
0 = Negative phase sequence.
1 = Positive phase sequence.
5
1 = Current exceeds FLC.
6
0 = Uninitialized.
1 = Initialized.
7
1 = Communication error between device and soft starter.
8–15
Reserved.
6.3.3 Bytes 4–5: Trip Code
Bits
Details
0–15
See the chapter Trip Codes.
6.3.4 Bytes 6–7: Motor Current
Bits
Details
0–15
Average rms current across all 3 phases.
6.3.5 Bytes 8–9: Motor Temperature
Bits
0–15
16 | Danfoss A/S © 2020.12
Details
Motor thermal model (%)
Packet Structures
AN353424578485en-000101 / 130R0947